80L Insulated Inergen IG 541 Inert Gas Fire Suppression System Without Residue
Insulated Inert Gas Inergen IG541 Fire Extinguishing System Without Residue
Characteristics of IG541 mixture gas fire extinguishing agent:
- It is called clean gas fire extinguishing agent, which is mixed by Nitrogen(50%), Argon(42%) and CO2(8%).
- Extinguishing mechanism is to reduce the concentration of oxygen in the combustion area to below the concentration needed to maintain the combustion, so as to realize asphyxiation and extinguishing, which is a pure physical effect.
- Low oxygen condition can ensure personnel’s lives and safety. When the gas is sprayed, it will not cause blurred vision, and will not produce chemical decomposition.
- No impact on electronic devices. When the gas is sprayed, the ambient temperature will only be reduced by 1-2 ℃, without condensation effect and electrostatic reaction, and without any residues and chemical decomposition.
- There in no impact on environment. Its ODP value is zero, and GWP value is zero, and ALT is also zero.
Parameters
| No. | Specification | Technical Parameter | |
| 1 | Working Pressure | 20MPa | 30MPa |
| 2 | Device Model | QMH20/80 | QMH30/80 |
| 3 | Capacity | 80Ltr | 80Ltr |
| 4 | Filling Capacity of Gas | 23.9kg | 33.2kg |
| 5 | Outside Diameter of Cylinder | Φ286mm | Φ286mm |
| 6 | Height of Cylinder | 1910mm | 1910mm |
| 7 | Spraying Time | ≤120s | ≤120s |
| 8 | Filling Rate | 0.299kg/L | 0.415kg/L |
| 9 | Power | DC24V/1.6A | DC24V/1.6A |
| 10 | Nitrogen Pressure of Driving Device | 6.0±1.0Mpa(20℃) | 6.0±1.0Mpa(20℃) |
| 11 | Condition of Reserving Room for Container | temperature: -20~50℃ | temperature: -20~50℃ |
| 12 | Max Working Pressure | 23.2MPa | 36.6MPa |
| 13 | Min Working Pressure | 18MPa | 27MPa |
Features and benefits
- Suitable for occupied areas
- Electrically non – conductive
- Chemically inert
- Colourless, odourless and flavourless
- No residue to clean up after the discharge
- Zero Ozone Depletion Potential (ODP)
- No greenhouse effect
- No global warming impact
- No decomposition products
- No fog and no loss of post-discharge visibility
- Non corrosive/toxic
- Stored as a gas
- Suitable for occupied areas
- Excellent post-discharge visibility
- Very low refill cost.
- Easy to obtain anywhere in the world
Application
Electronic computer room, a data processing center, telecommunications facilities, process control, expensive medical equipment, industrial equipment, library, museum and art gallery, clean room, anechoic chamber, emergency power facilities, flammable liquid storage area, etc.
The place where the fire is easy to happen, like paint-spraying production line, aging-electrical equipment, rolling machine, printing machine, oil switch, oil immersed transformer, melt impregnating tank, tank, large generators, drying equipment, cement pro duction process of pulverized coal, and the ship's engine room, cargo hold, etc.
Packages
We always pack it with polyfoam first and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.