Guangdong Air Giant Fire Equipment Co.,Ltd.
                                                                                                           
Verified Supplier
4 Years
Since 2022
Menu

Enclosed flooding Argonite IG 55 Gas Suppression System In Anechoic Chamber

Price Negotiable
Price: negotiation
MOQ: 1 set
Delivery Time: 10-15 working days
Brand: Air Giant
Product Description

Cylinder For Inert Gas Argonite IG55 Fire Extinguishing System Without Pollution In Anechoic Chamber

 

Inert gases are suited for extinguishment of fires in enclosed rooms. The Inert gas extinguishes the fire by diluting the oxygen concentration in Air to a level that cannot support combustion. The oxygen content I Air is approx 21%. In order to create an atmosphere that extinguishes the fire the oxygen level must be reduced to less that 15%. When introducing 50& Inertgas into an enclosure the oxygen level normally drops to 12,5% Inter gases are especially suited to extinguish fires in flammable liquids and gases, so called class B fires.

 

The Inert gases are also capable to suppress surface fires in class A fires, fires involving paper, textiles etc. Deep seated fires in class A materials is how ever a problem. Fires involving products that “bleeds” oxygen” can not be extinguished by Inert gases. Reactive products such as Magnesium and Titan or Metal hydrides can not be extinguished by Inert gases.

 

 

Parameters

 

No. Specification IG55(50% nitrogen;50% argon)
1 Capacity 80Ltr 140ltr
2 Working Pressure 20MPa 30MPa 20MPa 30MPa
3 Device Model QMH20/80 QMH30/80 QMH20/140 QMH30/140
4 Filling Capacity of Gas 22.32kg 33.48kg 42kg 58.2kg
5 Outside Diameter of Cylinder Φ279mm Φ267mm Φ406mm Φ356mm
6 Height of Cylinder 1710mm 1870mm 1460mm 1925mm
7 Filling Rate 0.299kg/L 0.415kg/L 0.300kg/L 0.201kg/L
8 Spraying Time ≤120s
9 Power DC24V/1.6A
10 Nitrogen Pressure of Driving Device 6.0±1.0MPa(20℃)
11 Condition of Reserving Room for Container temperature: 0~50℃
 

 

 

                    
 
 

Features and benefits

  1. Compared with the traditional 15MPa system, the 30MPa system saves 25%-50% of the quantity of extinguisher cylinders.
  2. It effectively reduces the floor area between the cylinders and improves the overall use value and utilization rate of the building.
  3. Constant low pressure release of 6MPa reduces the cost of piping and components for the whole system.
  4. The constant release pressure of 6MPa provides a more durable and effective pressure, with a transmission distance of up to 200 meters.
  5.  Whole system release by low pressure, it will be less impact on site personnel, equipment and building structure, and it will be more safety.

 

 

Application

 

Computer room, telecommunication room, transformer room, electrical switch and distribution room, generator room, leaching tank, drying equipment, paint spraying booth, electrical instrument room, control center, library, archives, treasure trove of cultural relics, etc.

 

 

Package

 

We always pack it with polyfoam firstly and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Guangdong Air Giant Fire Equipment Co.,Ltd.
Location Factory 101, Building 2, No. 2, Shaxing Road, Lanhe Town, Nansha District, Guangzhou,China
Contact Person Missaya Lu

Request A Quote

Please check your email address.
Your message must be at least 20 characters.