Features
Module I/O module  
Configuration method Via software (Flexi Soft Designer, Safe EFI-pro System: Safety Designer)  
Safety-related parameters
Safety integrity level SIL 3 (IEC 61508)  
Category Category 4 (EN ISO 13849)  
Performance level PL e (EN ISO 13849)  
PFHD (mean probability of a dangerous fail-
ure per hour)
4.8 x 10-9 (EN ISO 13849) 1)
0.9 x 10-9 (EN ISO 13849) 2)
 
TM (mission time) 20 years (EN ISO 13849)  
1) For single channel outputs.
2) For dual channel outputs.
Functions
Flexi Loop-compatible  
Fast shut-off  
Fast shut-off time 8 ms  
Interfaces
Number of safety inputs 8  
Number of test outputs 2  
Number of safe outputs 4  
Connection type Plug-in spring terminals  
2 SAFETY CONTROLLERS | SICK Product data sheet | 2024-11-27 22:21:16
  Subject to change without notice
  FX3-XTIO84002 | Flexi Soft
    SAFETY CONTROLLERS
Electrical data
Protection class III (EN 61140)  
Voltage supply Via FLEXBUS+  
Internal power consumption ≤ 2.2 W 1)  
Inputs
Input voltage HIGH
Input voltage LOW
Input current HIGH
Input current LOW

13 V DC ... 30 V DC

–5 V DC ... 5 V DC

2.4 mA ... 3.8 mA

–2.5 mA ... 2.1 mA
 
Test outputs    
Voltage supply Via FLEXBUS+  
Type of output PNP semiconductors, short-circuit protected  
Test pulse generator 2  
Output voltage HIGH 15 V DC ... 30 V DC  
Output current ≤ 120 mA 2)  
Outputs    
Voltage supply Via A1, A2  
Supply voltage 24 V DC (16.8 V DC ... 30 V DC)  
Type of supply voltage PELV or SELV 3)  
Type of output PNP semiconductors, short-circuit protected  
Output voltage HIGH 16 V DC ... 30 V DC  
Output current ≤ 2 A  
1) Via FLEXBUS+, without streams attest outputs.
2) On each of the two test pulse generators. This makes max. 8 testable safe series connections possible per module, each with max. 30 mA.
3) The current of the power supply that powers the module must be limited to a maximum of 4 A, either through the power supply itself or a fuse.
Mechanical data
Dimensions (W x H x D) 22.5 mm x 96.5 mm x 120.6 mm  
Weight 164 g (± 5 %)  
Ambient data
Enclosure rating IP20 (EN 60529)  
Ambient operating temperature –25 °C ... +55 °C  
Storage temperature –25 °C ... +70 °C  
Air humidity ≤ 95 %, Non-condensing  
Classifications
ECLASS 5.0 27243001  
ECLASS 5.1.4 27243101  
ECLASS 6.0 27243101  
ECLASS 6.2 27243101  
ECLASS 7.0 27243101  
ECLASS 8.0 27243101  
ECLASS 8.1 27243101  
ECLASS 9.0 27243101  
2024-11-27 22:21:16 | Product data sheet SAFETY CONTROLLERS | SICK 3
Subject to change without notice
FX3-XTIO84002 | Flexi Soft
SAFETY CONTROLLERS
ECLASS 10.0 27243101  
ECLASS 11.0 27243101  
ECLASS 12.0 27243101  
ETIM 5.0 EC001449  
ETIM 6.0 EC001449  
ETIM 7.0 EC001449  
ETIM 8.0 EC001449  
UNSPSC 16.0901 32151705  

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Xiamen ZhiCheng Automation Technology Co., Ltd
Location 903-3, building F02, phase III Software Park, Jimei district, Xiamen city,CHINA (361000)
Contact Person Andy

Request A Quote

Please check your email address.
Your message must be at least 20 characters.