NO Smart Differential Pressure Switch with Adjustable Set Point Max. Voltage 250VAC
Price:
$50.00/units >=10 units
MOQ:
10 units
Delivery Time:
Negotiable
Brand:
IVAN
Product Description
Product Description

Specification
model | DPS100A |
Maximum voltage | 250VAC |
Maximum current | 3A |
Output | Normally open or normally closed (SPDT) |
DP differential pressure set value / return difference | 10~100kPa |
DP hysteresis | 3~7kPa |
Maximum allowable static pressure | 14 bar |
Maximum allowable pressure difference | 14 bar |
Working medium | Oil / water / air (other media please specify when ordering) |
Operating temperature | -20℃~93℃ |
Setpoint repeatability deviation | ±1% |
Enclosure rating | IP54 |
Connector | 1/4” SAE(7/16”-20UNF) |


DPS series adjustable differential pressure switch can be used in oil, water and air fluid engineering to detect the pressure
difference of filters, pumps, heat exchangers, chillers and coils. When the pressure difference (flow rate) in the system rises or falls When the set value is reached, an alarm is output or an alarm of the cut-off function is provided to the automatic control system. It can also be used to indicate the status of the pump or filter. The differential pressure switch with adjustable set point can be directly calibrated by the factory according to customer requirements, and the calibration value is printed on the product label, and the user does not need to make adjustments on site. Customers can calibrate through professional instruments according to the pressure difference required by the equipment..
difference of filters, pumps, heat exchangers, chillers and coils. When the pressure difference (flow rate) in the system rises or falls When the set value is reached, an alarm is output or an alarm of the cut-off function is provided to the automatic control system. It can also be used to indicate the status of the pump or filter. The differential pressure switch with adjustable set point can be directly calibrated by the factory according to customer requirements, and the calibration value is printed on the product label, and the user does not need to make adjustments on site. Customers can calibrate through professional instruments according to the pressure difference required by the equipment..



The differential pressure switch with adjustable set point is installed at the inlet and outlet of the heat exchanger of the central air conditioning chiller. It can be used to detect the water flow of the heat exchanger. It is an accurate flow control method. It is based on the resistance and flow of the HVAC equipment. The curve design, we know that the heat exchanger, water filter, water pump and valve of HVAC equipment have performance curves of resistance and flow. We detect the difference between the inlet and outlet water pressure at both ends of the device and set it in advance with the device. The fixed value is compared to accurately control the flow. As a flow control switch, it has the characteristics of accurate flow control, no additional resistance to the system, no requirements on the pipe diameter and no disturbance of water flow disturbance. It can replace any form of target flow switch as the flow control of HVAC water system. Compared with the target type flow switch, it can avoid the false flow caused by the pump cavitation (the actual flow rate is large, but the water is mixed with air and the actual flow rate is not large), so it can be widely used in the use of brazed plate heat exchangers, casing Large and medium-sized air-cooled or water-cooled chillers with heat exchangers and shell-and-tube heat exchangers are used for water flow protection of the condenser and evaporator and also have the function of partial antifreeze protection..
Similar Products
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.
Company
Beijing Ifan Peng Instrument Co., Ltd.
Location
2006, Block C, Dongsheng Plaza, Shijiazhuang, Hebei, China
Contact Person
Kayla Pan