Conventional 2 Zone Fire Alarm Controller with 30 Detectors per Zone and 2A Power Supply for Wired Smoke Detection Systems
Price:
Negotiable
MOQ:
10PCS
Delivery Time:
3 Working days
Brand:
RISOL
Product Description
Product Overview
This conventional 2-zone fire alarm controller is designed to meet EN54 Parts 2 & 4 standards, providing sophisticated fire detection capabilities with straightforward operation and efficient installation. The system supports comprehensive integration with optical, ionization, photoelectric, and thermal detectors.
Key Features
- 2 conventional input zones supporting up to 30 detectors per zone
- 1 notification appliance circuit with built-in synchronization
- 2 amp power supply with 0.98A battery charging capacity
- Dedicated alarm and trouble relays
- RS485 connectivity for panel networking
- Compact metal enclosure (205mm W × 258mm H × 81mm D)
- Supports two 12V, 4Ah backup batteries
Technical Specifications
| Parameter | Specification |
|---|---|
| Primary AC Input | 120VAC/240VAC 50/60 Hz |
| Power Supply Rating | 2 Amps @ 24VDC |
| Maximum Battery Charging Current | 0.98 Amps @ 26VDC |
| Initiating Device Circuits | 2 Zones |
| Normal Operating Voltage | 23VDC, Maximum 26VDC |
| Maximum Detector Count per Zone | 30 detectors |
| NAC Current Rating | 1 Amp maximum per circuit |
| NAC Operating Voltage | 26VDC Nominal, 30VDC Maximum |
| Relay Ratings | 2A & 30VAC, resistive |
| Enclosure Dimensions | 205mm W × 258mm H × 81mm D |
Service & Support
- OEM & ODM services available
- Comprehensive technical support and after-sales service
- 1-year warranty coverage
- 15 working days standard lead time
- Sample orders welcome
Related Videos
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.
Company
Shenzhen Xinhe'an Technology Co., Ltd.
Location
406,Jude Building,Zhengfeng South Road,Fuyong Street,Bao'An District, Shenzhen City, Guangdong Province. China,518103
Contact Person
Claire