| Model |
HV500 Low Voltage Engineering Single-Drive Inverter |
iInput/output
Power |
Input Uin |
200V (-15%) ~240V (+10%) 3Phase , 380V (-15%) ~480V (+10%) 3Phase, |
| 500V (-15%) ~690V (+10%) 3Phase |
| Input Frequency |
50Hz/60Hz±5% |
| Unbalance Degree of Uin |
≤3% |
| Output Uout |
0V~Input Uin |
| Output Frequency |
0Hz~500Hz |
| Power range |
2.2kW~560kW |
Control
Performance |
Motor Type |
Asynchronous / Synchronous |
| Control Method |
V/F, OLVC (Open-Loop Vector Control), CLVC (Close-Loop Vector Control) |
| Range of Speed Regulation |
1:10 V/F, 1:100 OLVC, 1:1000 CLVC |
| Start Torque |
VF: 100% (0.5Hz), OLVC: 150% (0.5Hz), CLVC: 180% (0Hz) |
| Torque Precision |
≤5%, Vector Control |
| Torque Pulsation |
≤5%, Vector Control |
| Speed Regulation Precision |
OLVC 0.2%, CLVC 0.01% |
| Torque Response |
<5ms, Vector Control |
| Dynamic Speed Reduction |
OLVC<0.5%*s, CLVC<0.3%*s |
| Acceleration and Deceleration Time |
0.0s~3200.0s, 0.0min~3200.0min |
| Torque Lifting |
0.0%~30.0% |
| Overload |
Heavy Load Application 150% 1min/5min, Light Load Application 110% 1min/5min |
| V/F Curve |
Multiple ways: linear V/F curve, 5 kinds of torque reduction characteristic curve mode (2.0 power, 1.8 power, 1.6 power, 1.4 power, 1.2 power), user-defined VF curve |
| Input Frequency Accuracy |
Digital: 0.01Hz, Analog: 0.01Hz |
Control
Performance |
Acceleration and Deceleration Curve |
Straight, S Curve |
| Multiple Speed-Steps Operation |
16-Speed Steps Operation through control terminals |
| Automatic VoltageAdjustment (AVR) |
Keeping the output voltage constant automatically when the grid voltage changes within a certain range |
| Fixed Length |
Setted and Fixed Length Control |
| In-build PID |
It Can Easily Constructed Closed loop control system |
| Enhencement Function |
Free Function Block |
| iInput/output |
Set Frequency |
Keyboaed, UP/DOWN Terminals, Multiple Speed-Steps Operation, Terminals Pulsation, Com |
| Power |
| Analog Input Terminals |
AI1: 0V~10V/-10V~10V, AI2: 0V~10V/0(4) mA~20mA |
| Digital Input Terminals |
DI1-DI6, 6 programmable digital input terminals, optocoupler isolation, compatible with drain/source input |
| Digital Input/Output Terminals |
DIO1: Fast pulse output, normal input/output; DIO2: fast pulse input, normal input/output |
| Anolog Output Terminals |
2 Strings 0V~10V/0 (4) mA~20mA |
| Relay Output |
2Strings Contact Type FormC |
| Motor Temperature Detection |
Support PT100/PT1000/KTY84 |
| STO Interface |
SIL3/PLe Safe torque shutdown function |
| Com |
Com Protocol |
Modbus RTU (Standard), Profibus,CANopen,profinet,Devicenet,ControlNet |
| profinet,Devicenet,ControlNet |
| t |
| Environment |
Altitude |
Without Derating Operation Within 2000m Altitude; 2000m~4000m, Each 100m lifting, Derating 1% (Current) |
| Operation Temperature |
-25℃~+40℃ (40℃~55℃ Derating) |
| Humidity |
15%~95%, Without Condensation |
| Vibration |
3M3, IEC60721-3-3 |
| Storage Temperature |
-40℃~+70℃ |
| Operation Place |
Indoor, Without direct sunlight, no flammable, corrosive gases, liquids and conductive particles |
| Accessory |
Encoding card, communication expansion card, voltage detection card |
| Protection Function |
Short circuit, over current, overload, over voltage, under voltage, phase loss, over temperature, external fault, etc. |
| Efficiency |
5.5kW~22kW: ≥93%; Above 30kW: ≥95% |
| Installation Method |
Cabinet |
| Protection Degree |
IP20 |
| Cooling |
Forced Air Cooling |