Pt100 HART Head Mounted Temperature Transmitter TMT192C Field Communication
Pt100 HART Head Mounted Temperature Transmitter tMT192C Field communication
Overview:
The TMT192C is a versatile head-mounted temperature transmitter designed for use with resistance thermometers (RTD), thermocouples (TC), and both resistance and voltage transmitters. It is configurable via the HART protocol, ensuring high performance and reliability across various applications.
Key Features:
- Wide Sensor Compatibility: Accepts multiple input types including RTDs, thermocouples, resistance transmitters, and voltage transmitters.
- HART Digital Communication: Facilitates easy configuration and diagnostics.
- Self-Diagnostic Functionality: Monitors performance and alerts for any issues.
- Analog Output: Converts diverse input signals into a scalable 4 to 20 mA analogue output.
Performance Specifications:
- Universal Input Settings: Supports various sensor inputs with adjustable settings.
- 2-Wire Technology: Simplifies installation with a 4 to 20 mA analogue output.
- High Accuracy: Maintains precise measurements across a broad ambient temperature range.
- Galvanic Isolation: Ensures safety and signal integrity.
- Internal Temperature Compensation: Features an internal sensor for active temperature compensation (specifically for thermocouples).
- Wide Voltage Supply Range: Accommodates diverse power supply options.
- Custom Measurement Ranges: Allows for tailored settings to meet specific application needs.
- Expanded Input Capabilities: Supports resistance inputs up to 2 kΩ and voltage inputs up to 2 mV.
Applications:
Ideal for various industrial applications that require accurate temperature measurement and conversion.
| Input | Type | Measurement Ranges | Min.meas.ranges |
| Resistance thermonmeter(RTD) | PT100 | -200℃ to 850℃(-328℉ to 1562℉) | 10K |
| Resistance thermonmeter(RTD) | PT500 |
►-200℃ to 250℃(-328℉ to 482℉) |
10K |
| Resistance thermonmeter(RTD) | PT1000 | -200℃ to 250℃(-328℉ to 482℉) | 10K |
| Resistance thermonmeter(RTD) | Cu50 | ►-50℃ to 150℃(-58℉ to 302℉) | 10K |
| Resistance thermonmeter(RTD) | Cu100 | ►-50℃ to 150℃(-58℉ to 302℉) | 10K |
| Resistance thermonmeter(RTD) | Ni100 | ►-60℃ to 180℃(-76℉ to 356℉) | 10K |
| Resistance thermonmeter(RTD) | Ni500 | ►-60℃ to 180℃(-76℉ to 356℉) | 10K |
| Resistance thermonmeter(RTD) | Ni1000 | ►-60℃ to 150℃(-76℉ to 302℉) | 10K |
| Resistance thermonmeter(RTD) | Resistance(Ω) | 0Ω to 400Ω | 10Ω |
| Resistance thermonmeter(RTD) | Resistance(Ω) | 0Ω to 2000Ω | 20Ω |
| Connection type: 2-wire, 3wire, 4wire connection | |||
| Thermocouples (TC) |
B(PtR30-PtRh6) | 0℃ to 180℃(-32℉ to 3308℉) | 500K |
| Thermocouples (TC) |
E(NiCr-CuNi) | -270℃ to 1000℃(-454℉ to 1832℉) | 50K |
| Thermocouples (TC) |
J(Fe-CuNi) | -210℃ to 1200℃(-346℉ to 2192℉) | 50K |
| Thermocouples (TC) |
K(NiCr-Ni) | -270℃ to 1372℃(-454℉ to 2501℉) | 50K |
| Thermocouples (TC) |
N(NiCrSi-NiSi) | -270℃ to 1300℃(-346℉ to 2372℉) | 50K |
| Thermocouples (TC) |
R(PtRh13-Pt) | -50℃ to 1768℃(-58℉ to 3214.4℉) | 500K |
| Thermocouples (TC) |
S(PtRh10-Pt) | -50℃ to 1768℃(-58℉ to 3214.4℉) | 500K |
| Thermocouples (TC) |
T(Cu-CuNi) | -270℃ to 400℃(-454℉ to 752℉) | 50K |
| Voltage transmitters(mV) | Millivolt transmitter(mV) | -75mV to 75V | 5mV |
| Voltage transmitters(mV) | Millivolt transmitter(mV) | -700mV to 200V | 20mV |
| ► ON Request | |||
Ordering code
| Certification | |||||||
| A B |
Version for non hazardous areas NEPSI Ex ia CT4 |
||||||
| Configuration transmitter connection | |||||||
| A 1 2 3 4 |
Standard factory configuration 3-wire | ||||||
| Configuration Configuration Configuration Configuration |
connection TC connection RTD(2-wire) connection RTD(3-wire) connection RTD(4-wire) |
||||||
| Configuration temperature sensor | |||||||
| A 1 2 3 4 5 6 7 8 B E J K N R S T |
Standard factory configuration Pt100 Pt100-200℃ to 850℃(-328°Fto 1562°F) Pt500-200℃ to 250℃(-328°F to 482"F) Pt500-200℃ to 250℃(-328F to 482°F) Pt1000-200℃ to 250℃(-328°F to 482°F) Cu50 -50℃ to 150℃(-58°F to 302°F) Cu100-50℃ to 150℃(-58°F to 302°F) Ni100-60℃ to 180℃ (-76°Fto 356°F) Ni500-60℃ to 180℃(-76°Fto 356°F) Type B 0℃ to 1820℃(-32°F to 3308°F Type E -270℃ to 1000℃(-454F to 1832°F) Type J-210℃ to 1200℃(-346°Fto 2192°F) Type K-270℃ to 1372℃(-454°F to 2501F) Type N -270℃ to 1300℃(-454°F to 2372°F) Type R -50℃ to 1768℃(-58°F to 3214.4°F) Type S-50℃ to 1768℃(-58°Fto 3214.4°F) Type T -270℃ to 400℃(-454°F to 752°F) |
||||||
| Configuration | |||||||
| A B C D |
Standard factory configuration(Pt100/3-wire/0 to 100℃) Customised measurement range Customised expanded configuration for TC Customised expanded configuration for RTD |
||||||
| TMT192C | Order code(complete) For example:TMT192CA-AAAA | ||||||
SENSE INSTRUMENTS has specialized in the development and production of temperature transmitters for three decades. Our seasoned research and development team offers extensive expertise, ensuring that all our products include PC-side debugging software. We excel in providing customized software solutions to meet our clients' specific requirements, with OEM customization as a core strength. Our HART temperature transmitters come equipped with DD files and support debugging via handheld communicators.
Dimensions
How to programme
Install
Get in Touch