480V 240kVA To 720kVA Modular UPS Power Supply 3 Phase Customizable
Price:
Negotiable
MOQ:
1PC
Delivery Time:
8 work days
Brand:
kimoems or OEM
Product Description
(480V)240kVA to 720kVA Modular Ups Power Supply 60kw Power Module
Parameters
| Model | AC240/60-H | AC360/60-H | AC500/62.5-H | AC600/60-H | AC720/60-H |
|---|---|---|---|---|---|
| Rate Power | 240kVA/240kW | 360kVA/360kW | 500kVA/500kW | 600kVA/600kW | 720kVA/720kW |
| Input | 3P5W (3P+N+PE) | 3P5W (3P+N+PE) | 3P5W (3P+N+PE) | 3P5W (3P+N+PE) | 3P5W (3P+N+PE) |
| Input Rate Voltage | 480VAC(L-L) | 480VAC(L-L) | 480VAC(L-L) | 480VAC(L-L) | 480VAC(L-L) |
| Input Rate Freq. | 50/60Hz | 50/60Hz | 50/60Hz | 50/60Hz | 50/60Hz |
| Input PF | >0.99 | >0.99 | >0.99 | >0.99 | >0.99 |
| Input Current distortion | THDi<3%(100% Linear load) | THDi<3%(100% Linear load) | THDi<3%(100% Linear load) | THDi<3%(100% Linear load) | THDi<3%(100% Linear load) |
| Input Voltage range | 384 ~ 528VAC(L-L) full load; 288 ~ 384VAC (L-L) power derate from 100% to 75% | 384 ~ 528VAC(L-L) full load; 288 ~ 384VAC (L-L) power derate from 100% to 75% | 384 ~ 528VAC(L-L) full load; 288 ~ 384VAC (L-L) power derate from 100% to 75% | 384 ~ 528VAC(L-L) full load; 288 ~ 384VAC (L-L) power derate from 100% to 75% | 384 ~ 528VAC(L-L) full load; 288 ~ 384VAC (L-L) power derate from 100% to 75% |
| Input Freq. range | 40-70Hz | 40-70Hz | 40-70Hz | 40-70Hz | 40-70Hz |
| Battery Rate voltage | ±240VDC | ±240VDC | ±240VDC | ±240VDC | ±240VDC |
| Battery Charging capacity | 20%*Pout | 20%*Pout | 20%*Pout | 20%*Pout | 20%*Pout |
| Battery Charging accuracy | ±1% | ±1% | ±1% | ±1% | ±1% |
| Bypass Rate voltage | 480VAC(L-L) | 480VAC(L-L) | 480VAC(L-L) | 480VAC(L-L) | 480VAC(L-L) |
| Bypass Voltage range | Range: -40%~ +25%, Settable, default -20%~ +15% | Range: -40%~ +25%, Settable, default -20%~ +15% | Range: -40%~ +25%, Settable, default -20%~ +15% | Range: -40%~ +25%, Settable, default -20%~ +15% | Range: -40%~ +25%, Settable, default -20%~ +15% |
| Bypass Overload | 125%, long time operation 125%<load <130%, 10mins 130%<load <150%,1min >150%,300ms | 110%, long time operation 110%<load <125%, 5 mins 125%<load <150%,1 min >150%,1 second | 110%, long time operation 110%<load <125%, 5 mins 125%<load <150%,1 min >150%,1 second | 110%, long time operation 110%<load <125%, 5 mins 125%<load <150%,1 min >150%,1 second | 110%, long time operation 110%<load <125%, 5 mins 125%<load <150%,1 min >150%,1 second |
| Inverter Rate voltage | 480VAC(L-L) | 480VAC(L-L) | 480VAC(L-L) | 480VAC(L-L) | 480VAC(L-L) |
| Inverter Rate Freq | 50/60Hz | 50/60Hz | 50/60Hz | 50/60Hz | 50/60Hz |
| Inverter Output PF | 1 | 1 | 1 | 1 | 1 |
| Inverter Voltage accuracy | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% |
| Inverter Load response | <5% (20% - 80% -20% step load) | <5% (20% - 80% -20% step load) | <5% (20% - 80% -20% step load) | <5% (20% - 80% -20% step load) | <5% (20% - 80% -20% step load) |
| Inverter Recovery time | <20ms (0% - 100% -0% step load) | <20ms (0% - 100% -0% step load) | <20ms (0% - 100% -0% step load) | <20ms (0% - 100% -0% step load) | <20ms (0% - 100% -0% step load) |
| Inverter Output THDu | <1%(Linear load),<5% (non-Linear load according to IEC 62040-3) | <1%(Linear load),<5% (non-Linear load according to IEC 62040-3) | <1%(Linear load),<5% (non-Linear load according to IEC 62040-3) | <1%(Linear load),<5% (non-Linear load according to IEC 62040-3) | <1%(Linear load),<5% (non-Linear load according to IEC 62040-3) |
| Inverter Overload | 110%,1 hour; 125%,10 mins; 150%,1 min; >150%,200ms | 110%,1 hour; 125%,10 mins; 150%,1 min; >150%,200ms | 110%,1 hour; 125%,10 mins; 150%,1 min; >150%,200ms | 110%,1 hour; 125%,10 mins; 150%,1 min; >150%,200ms | 110%,1 hour; 125%,10 mins; 150%,1 min; >150%,200ms |
| Inverter Frequency accuracy | 0.1% | 0.1% | 0.1% | 0.1% | 0.1% |
| Inverter Synchronize window | Settable, ±0.5Hz-±5Hz, default ±3Hz | Settable, ±0.5Hz-±5Hz, default ±3Hz | Settable, ±0.5Hz-±5Hz, default ±3Hz | Settable, ±0.5Hz-±5Hz, default ±3Hz | Settable, ±0.5Hz-±5Hz, default ±3Hz |
| Inverter Slew rate | Settable, 0.5Hz/S-3Hz/S, default 0.5Hz/S | Settable, 0.5Hz/S-3Hz/S, default 0.5Hz/S | Settable, 0.5Hz/S-3Hz/S, default 0.5Hz/S | Settable, 0.5Hz/S-3Hz/S, default 0.5Hz/S | Settable, 0.5Hz/S-3Hz/S, default 0.5Hz/S |
| Inverter Crest factor | 3:1 | 3:1 | 3:1 | 3:1 | 3:1 |
| Inverter Phase Accuracy | 120°±0.5° | 120°±0.5° | 120°±0.5° | 120°±0.5° | 120°±0.5° |
| System Efficiency | Normal Mode up to 96%; Battery Mode up to 96% | Normal Mode up to 96%; Battery Mode up to 96% | Normal Mode up to 96%; Battery Mode up to 96% | Normal Mode up to 96%; Battery Mode up to 96% | Normal Mode up to 96%; Battery Mode up to 96% |
| System Display | LED + 7 inch touch LCD | LED + 10 inch touch LCD | LED + 10 inch touch LCD | LED + 10 inch touch LCD | LED + 10 inch touch LCD |
| System Certification- Safety | IEC62040-1; IEC60950-1 | IEC62040-1; IEC60950-1 | IEC62040-1; IEC60950-1 | IEC62040-1; IEC60950-1 | IEC62040-1; IEC60950-1 |
| System Certification- EMS | IEC62040-2; IEC61000-4-2(ESD); IEC61000-4-3(RS); IEC61000-4-4 (EFT); IEC61000-4-5 (Surge) | IEC62040-2; IEC61000-4-2(ESD); IEC61000-4-3(RS); IEC61000-4-4 (EFT); IEC61000-4-5 (Surge) | IEC62040-2; IEC61000-4-2(ESD); IEC61000-4-3(RS); IEC61000-4-4 (EFT); IEC61000-4-5 (Surge) | IEC62040-2; IEC61000-4-2(ESD); IEC61000-4-3(RS); IEC61000-4-4 (EFT); IEC61000-4-5 (Surge) | IEC62040-2; IEC61000-4-2(ESD); IEC61000-4-3(RS); IEC61000-4-4 (EFT); IEC61000-4-5 (Surge) |
| System IP degree | IP20 | IP20 | IP20 | IP20 | IP20 |
| System Configuration | USB, RS232, RS485, Dry contact, Cold start, Air filter | USB, RS232, RS485, Dry contact, Cold start, Air filter | USB, RS232, RS485, Dry contact, Cold start, Air filter | USB, RS232, RS485, Dry contact, Cold start, Air filter | USB, RS232, RS485, Dry contact, Cold start, Air filter |
| System Option | SNMP card, AS400 card, Parallel kit, SPD, LBS | SNMP card, AS400 card, Parallel kit, SPD, LBS | SNMP card, AS400 card, Parallel kit, SPD, LBS | SNMP card, AS400 card, Parallel kit, SPD, LBS | SNMP card, AS400 card, Parallel kit, SPD, LBS |
| System Environment | 0-40℃ (operation); -25℃-70℃ (storage); 0-95% (Humidity, non-condensing ) | 0-40℃ (operation); -25℃-70℃ (storage); 0-95% (Humidity, non-condensing ) | 0-40℃ (operation); -25℃-70℃ (storage); 0-95% (Humidity, non-condensing ) | 0-40℃ (operation); -25℃-70℃ (storage); 0-95% (Humidity, non-condensing ) | 0-40℃ (operation); -25℃-70℃ (storage); 0-95% (Humidity, non-condensing ) |
| System Noise(dB)(1 meter) | 72dB @ 100% load, 69dB @ 45% load | 72dB @ 100% load, 69dB @ 45% load | 72dB @ 100% load, 69dB @ 45% load | 72dB @ 100% load, 69dB @ 45% load | 72dB @ 100% load, 69dB @ 45% load |
| Dimension Cabinet(WDH)mm | 600*1000*1600 | 600*1000*2000 | 1200*1000*2000 | 1200*1100*2000 | 120011002000 |
| Dimension Module(WDH)mm | 442*659*174 | 442*659*174 | 442*659*174 | 442*659*174 | 442*659*174 |
| Weight(kg) Cabinet | 185 | 248 | 250 | 578 | 578 |
| Weight(kg) Module | 41 | 41 | 41 | 41 | 41 |
| Power Module rated capacity | 60KW | 60KW | 62.5KW | 60KW | 60KW |
Similar Products
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.
Company
Hefei Kimo Electrical Co.,Ltd
Location
Building 3, Tuoji Park, No.691, Chang jiang West Road, Shushan District, Hefei, Anhui Province
Contact Person
Emma