Type Steel Structure Fireproof Coating Sample test Furnace,Is Suitable for Tests on Various Fireproof Coatings for Steel Structures Used Both Indoors And Outdoors In Buildings
This tester complies with the technical indicators and requirements stipulated in the national standards GB/T9978-2008 and GB/T14907-2002, and is suitable for
Tests on various fireproof coatings for steel structures used both indoors and outdoors in buildings (structures).
Ii. Detailed Parameters
Ambient temperature: Room temperature to 40℃;
Relative humidity: ≤75%.
3. Working environment: Indoor without forced ventilation.
2. Power supply voltage: AC220V±10V, 50HZ.
4. Combustion gas source: natural gas, liquefied petroleum gas.
5. Degree of temperature increase: Room temperature to 1150℃ for 4 hours.
6. Back temperature alarm: 180℃-220℃+2℃.
7. Digital display of temperature.
8. Automatically control the time-temperature rise curve and record it.
9. Automatic adjustment of air supply volume; Pressure measurement range: 0-100Pa, accuracy 0.15Pa.
10. Internal dimensions of the furnace: length 1.5m* width 0.8m* height 1.2m.
11. Sample size: 5007 pieces of 116 I-beams in length
Three pieces of 140b I-beams
12. Microcomputer control, programmed temperature rise, and automatic formatted printing of test result reports.