Ningbo Macwey Industrial Technology Co.,Ltd
                                                                                                           
Verified Supplier
13 Years
Since 2013
Menu

Industrial AC Vacuum Contactor 2.5kA 1140V 250A Contactor For Industrial Applications

Price Negotiable
Price: $300
MOQ: 1 piece
Delivery Time: 20 days
Brand: MacweyTEK
Product Description
Vacuum Contactor VK49-1.14-2.5250 AC Contactor with 250A 2.5kA 1140V for Industrial Applications
High-performance vacuum contactor model VK49-1.14-2.5250 rated at 250A, 2.5kA breaking capacity, and 1140V operation.
Product Overview
This series contactor consists of an electrical insulating frame, metal base, shaft and crank arm, electromagnetic systems, permanent magnet, power modules, auxiliary switches, and vacuum interrupters.
Operating Principle
When control voltage is applied to the electromagnetic coil, the armature drives the crutch rotating to open the main contact in the vacuum interrupter. The auxiliary switch simultaneously cuts off power to the electromagnetic coil, transitioning to permanent-magnet maintenance. After power is interrupted by the control circuit, energy storage from the power module discharges to the electromagnetic coil for degaussing, and the main contact opens under the function of the opening spring.
Normal Operating Conditions
  • Environment temperature: -5°C to +40°C, with 24-hour average not exceeding +35°C
  • Altitude: No more than 1000m
  • Atmospheric conditions: Monthly highest humidity ≤90% in wettest month, monthly average minimum temperature 25°C
  • Impact vibration: Location without extensive shaking, impact, or vibration
  • No explosion hazards, enchant gas, or sleet
  • No rain and snow in installation area
  • Pollution degree: Grade 3
  • Installation type: III
  • Installation condition: Slant angle between installation surface and vertical surface ≤15°
Technical Specifications
KVT-6 Series (6-7.2kV)
Item Unit KVT-6-1.6/160 KVT-6-2.5/250 KVT-6-4/400 KVT-6-6.3/630
Contact Group quantity 3+3p (3NO+3NC)
Main Circuit Rated Voltage kV 6-7.2
Main Circuit Rated Current A 160 250 400 630
Rated Breaking Current (Ics) kA 1.6 2.5 4 6.3
Main Circuit Current Making Capacity A/100 times 1600 2500 4000 6300
Main Circuit Make-Break Capacity A/25 times 1280 2000 3200 5000
Maximum Breaking Capacity A/3 times 3200 3200 4000 6300
KVT-10 Series (10-12kV)
Item Unit KVT-10-1.6/160 KVT-10-2.5/250 KVT-10-4/400 KVT-10-6.3/630
Contact Group quantity 3+3p (3NO+3NC)
Main Circuit Rated Voltage kV 10-12
Main Circuit Rated Current A 160 250 400 630
Rated Breaking Current (Ics) kA 1.6 2.5 4 6.3
Main Circuit Current Making Capacity A/100 times 1600 2500 4000 6300
Main Circuit Make-Break Capacity A/25 times 1280 2000 3200 5000
Maximum Breaking Capacity A/3 times 3200 3200 4000 6300
General Specifications
Mechanical Life times 1,000,000
Power Frequency Withstand Voltage (Main Circuit) kV 32 (6kV series) 42 (10kV series)
Power Frequency Withstand Voltage (Auxiliary) kV 2.5
Power Frequency Withstand Voltage (Control) kV 2
Rated Operating Frequency times/h 300
Opening Time ms ≤120
Closing Time ms ≤150
Clearance Between Open Contacts mm 4±0.5 (6kV series) 5±0.5 (10kV series)
Over Travel mm ≥1.2
Overall Dimensions (L×H×B) mm 468×540×200

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Ningbo Macwey Industrial Technology Co.,Ltd
Location No.218, Weier Road, Chongshou Industrial Park, Cixi City (Ningbo), China
Contact Person Alec Sung

Request A Quote

Please check your email address.
Your message must be at least 20 characters.