SDCS-IOE-2 61208097 ABB DCS-800 DC Drive I/O Extension Board
Product Snapshot
SDCS-IOE-2 (ABB PN 61208097) is a plug-in I/O extension board for DCS-800 DC converters. It adds 16 digital inputs, 8 digital outputs, 4 analog inputs and 2 analog outputs to the standard DCS-800 control interface, eliminating external I/O modules and reducing panel wiring by > 30%. On-board 24 VDC supply, short-circuit protection and LED diagnostics make it the default choice for paper, metals, crane and marine DC-drive retrofits.
Key Features & Benefits
- 32 mixed-signal I/O - 16 DI, 8 DO, 4 AI, 2 AO in one slot
- 24 VDC on-board supply - 0.5 A for sensors, protected & monitored
- Galvanic isolation - 1 500 V channel-to-logic, 500 V channel-to-channel
- Plug-and-play - DIN-rail clip, hot-swap, LED status for every point
- Wide temperature - 0…+70 °C operating, -40…+85 °C storage
- Global certs - CE, UL 508, ABS marine, RoHS, REACH
Technical Specifications
| Part Number | SDCS-IOE-2 61208097 |
| Function | I/O extension board for DCS-800 |
| Digital Inputs | 16 × 24 VDC, 2 ms filter, IEC 61131-2 type 3 |
| Digital Outputs | 8 × 24 VDC, 0.5 A, short-circuit proof |
| Analog Inputs | 4 × ±10 V / 0-20 mA / 4-20 mA, 12-bit, configurable |
| Analog Outputs | 2 × ±10 V / 0-20 mA, 12-bit, configurable |
| Isolation | 1 500 V RMS channel-to-logic |
| On-board Supply | 24 VDC ±10 %, 0.5 A for sensors |
| Update Time | 1 ms digital, 2 ms analog |
| Dimensions (W×H×D) | 100 × 22.5 × 115 mm |
| Weight | 0.17 kg |
| Operating Temp | 0 - 70 °C |
| Storage Temp | -40 - +85 °C |
| Humidity | 95 % RH non-condensing |
| Protection | IP20 |
| Certifications | CE, UL 508, ABS, RoHS |
Typical Applications
- Paper machine sectional DC drives (tension & speed loops)
- Metals rolling-mill stand controls (torque & position)
- Crane hoist and travel drives (load-sharing)
- Marine thruster DC drives (ABS certified)
- Retrofit of DCS-500/600 systems needing extra I/O
Compatible Drives / CPUs
- DC Converters: DCS-800 (all frame sizes A-R)
- Inverters: ACS-800-U11 (when used as DC-bus supply)
- PLC Interface: CI-858, CI-867 via DriveBus or Modbus-TCP
- Legacy Upgrade: Replaces SDCS-IOB-3 + external I/O racks
Installation & Start-up
- Mount board on 35 mm DIN-rail inside DCS-800; clip until latch clicks.
- Wire I/O - use shielded pairs, earth shield at panel entry only.
- Connect 24 V - observe polarity; green "PWR" LED lights.
- Configure drive - select "IOE-2" in DriveStudio, set ranges & scaling.
- Test signals - force a DO, measure 24 V; inject 4 mA into AI, verify count.
LED Diagnostics
| LED | Color | Meaning |
|---|---|---|
| PWR | Green | 24 V supply OK |
| DI 0-15 | Yellow | Input active |
| DO 0-7 | Yellow | Output active |
| AI/AO | Green blink | Conversion in progress |
| FAULT | Red | Over-current, under-voltage |