IP68 Fireproof Waterproof Bus Bar Trunking System 400-5000A with 180-Minute Fire Resistance
Our comprehensive range of busbar trunking systems offers customizable solutions for industrial power distribution applications with enhanced safety and reliability features.
| Current Level (A) | XLC /4P Width (mm) | XLC /4P Height (mm) | XLC /5P Width (mm) | XLC /5P Height (mm) |
|---|---|---|---|---|
| 400 | 128 | 98 | 128 | 98 |
| 500 | 128 | 108 | 128 | 108 |
| 630 | 128 | 123 | 128 | 123 |
| 800 | 128 | 138 | 128 | 138 |
| 1000 | 128 | 158 | 128 | 158 |
| 1250 | 128 | 183 | 128 | 183 |
| 1600 | 128 | 218 | 128 | 218 |
| 2000 | 128 | 268 | 128 | 268 |
| 2500 | 128 | 280 | 128 | 280 |
| 3200 | 128 | 400 | 128 | 400 |
| 4000 | 128 | 490 | 128 | 490 |
| Execution Standards | IEC60439.1-2000, IEC60439.2-2000, GB/T 7251.6-2015 |
| Ambient Temperature | -5°C to +40°C (24-hour average ≤35°C) |
| Altitude | ≤2000M |
| Protection Grade | IP54, IP66 |
| Unit Length (M) | 1.6, 2.5, 3.2, 6 (0.5-6) |
| Rated Operational Voltage (V) | 690V (with tap unit)/1000V (without tap unit) |
| Rated Insulation Voltage (Ui) (V) | 800V (with tap unit)/1000V (without tap unit) |
| Frequency (HZ) | 50-60 |
| Rated Current (A) | 400-5000 |
| Temperature Rise (K) | ≤70 |
| Insulation Resistance (MΩ) | ≥20 |
| Installation Method | Vertical or horizontal |
- Enhanced safety with double-grounded shell protection
- Strong overload capacity with low temperature rise (≤70K)
- Excellent load capacity and dynamic/thermal stability
- Eliminates uneven current distribution in spliced cables
- Good short-circuit resistance with low energy consumption
- Easy maintenance with quick disassembly/assembly
Power supply systems for large factories, mining operations, substations, and captive power plants, from generators to transformers and high-voltage distribution rooms.
- Capacity range: 100A to 4000A
- IP68 protection rating (100% waterproof and dustproof)
- Epoxy resin casting prevents oxidation and corrosion
- Compact structure with strong mechanical properties
- Suitable for harsh indoor/outdoor environments
- Capable of continuous overload operation
Applications: Power plants, substations, shipbuilding, paper mills, ports, basements, petrochemical plants, steel mills, coal mines, and other demanding environments.
- 180-minute fire resistance rating
- Compact structure with minimal footprint
- Fire-resistant paint and baffles prevent flame penetration
- Low impedance with excellent stability
- Materials withstand temperatures up to 1000°C
Applications: Schools, hospitals, hotels, financial buildings, offices, urban transit, government buildings, libraries, textile plants, and mining operations.
Get in Touch