MTL5576-RTD MTL Safety Barrier Resistance Temperature Detectors

Price Negotiable
Price: Negotiable
MOQ: 1
Delivery Time: 3 working days
Brand: MTL
Product Description
MTL5576-RTD Safety Barrier Resistance Temperature Detectors
The Eaton Crouse-Hinds series MTL5500 temperature converter is a 2-channel safety barrier designed for hazardous locations. This robust device accepts 2- or 3-wire RTD inputs with a 0-400 ohms signal range and provides comprehensive LED status indication.
Product Overview
Product Name Eaton Crouse-Hinds series MTL5500 temperature converter
Catalog Number MTL5576-RTD
Product Type Temperature converter
Dimensions (L x H x W) 109.8 mm × 118.8 mm × 15.8 mm
Product Weight 150 g
Key Features
  • 2-channel RTD/potentiometer input with 0-400Ω signal range
  • Hazardous location certified for Zone 0 applications
  • Functional channel-channel isolation for enhanced safety
  • Comprehensive LED status indication (Green=power, Yellow=status, Red=LFD)
  • Configurable response time with 500ms default setting
  • Safety drive options on sensor failure (upscale, downscale, or off)
Technical Specifications
Input Signal 2-, 3-wire RTDs
Signal Range 0-400Ω
Output Signal Range 4-20mA nominal into 300Ω max.
Number of Channels 2
Power Supply 20-35 Vdc
Current Consumption 60mA
Power Dissipation 1.4W
RTD Excitation Current 200µA
Transfer Accuracy ±16µA
Temperature Drift ±0.6µA/°C
Response Time Configurable (500ms default)
Operating Temperature -20°C to 60°C
Storage Temperature -40°C to 80°C
Humidity 5-95% relative humidity
Common Mode Rejection 120 dB for 240V at 50 or 60 Hz
Series Mode Rejection 40 dB for 50 or 60 Hz
Mounting Method T-section 35mm DIN rail
Terminal Capacity Accepts conductors up to 2.5mm² stranded or single-core
Electrical Connection Crimp ferrules
Configuration Personal computer running MTL PCS45 software with PCL45USB serial interface
Safety & Certification
Area Classification Hazardous/Classified Locations
Standards Type IEC, IECEx/ATEX
Hazardous Rating Zone 0
Galvanic Isolation 250V rms between safe-area circuits and power supply
EMC Compliance EN61326
MTL5576-RTD Temperature Converter Safety Barrier

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Shenzhen Hengyo Power Technology Co., Limited
Location Room 2407, B Block No.145 Chengshi Zhuchang Bld, Bagua 2nd Rd, Futian Dist. Shenzhen City, China 518029
Contact Person Vivian Chan

Request A Quote

Please check your email address.
Your message must be at least 20 characters.