MTL5576THC MTL Intrinsic Safety Isolators Temperature Converter Safe Barrier
Price:
Negotiable
MOQ:
1
Delivery Time:
3 working days
Brand:
MTL
Product Description
MTL5576THC MTL Intrinsic Safety Isolators Temperature Converter
Eaton Crouse-Hinds series MTL5500 temperature converter with 2-channel configuration, designed for temperature input applications. Features 20-35 Vdc power supply, 1.4W power dissipation, and 60mA current consumption. Accepts THC type input signals with -75mV to +75mV range and provides comprehensive LED status indication.
| Product Name | Eaton Crouse-Hinds series MTL5500 temperature converter |
| Catalog Number | MTL5576-THC |
| Product Dimensions | 109.8 mm (Length/Depth) * 118.8 mm (Height) * 15.8 mm (Width) |
| Product Weight | 150 g |
| Global Catalog | MTL5576-THC |
| Product Type | Temperature converter |
Technical Specifications
| Type | mV/THC input |
| Area Classification | Hazardous/Classified Locations |
| Standards Type | IECEx/ATEX IEC |
| IECEx/ATEX Hazardous Rating | Zone 0 |
| Operating Temperature Range | -20°C to 60°C |
| Storage Temperature Range | -40°C to 80°C |
| Humidity | 5-95% relative humidity |
| Signal Type | Temperature input |
| Signal Range | -75mV to +75mV |
| Response Time | Configurable (500ms default) |
| Output Signal Range | 4-20mA nominal into 300Ω max. |
| Number of Channels | 2 |
| Terminal Capacity | Accepts conductors of up to 2.5mm² stranded or single-core |
| Mounting Method | T-section 35mm DIN rail |
| EMC | EN61326 |
| Safety Drive on Sensor Failure | Upscale, downscale, or off |
| Configuration | Personal computer running MTL PCS45 software with PCL45USB serial interface |
| Cold Junction Compensation Error | ≤1.0°C |
| Cold Junction Compensation | Automatic or selectable |
| Common Mode Rejection | 120 dB for 240V at 50 or 60 Hz |
| Series Mode Rejection | 40 dB for 50 or 60 Hz |
| Electrical Connection | Crimp ferrules |
| Power Supply | 20-35 Vdc |
| Current Consumption | 60mA |
| Galvanic Isolation | 250V rms between safe-area circuits and power supply |
| Galvanic Separation | Functional channel-channel isolation for safe and hazardous area circuits |
| LED Indication | Yes |
| LED Colors | Green (Power), Yellow (Status), Red (LFD) |
| Power Dissipation | 1.4W |
| Input Signal | THC types, mV |
| Maximum Load Resistance | >10kΩ (safety drive disabled) 300Ω (safety drive enabled) |
| Transfer Accuracy | ±16µA |
| Temperature Drift | ±0.6µA/°C |
Key Features
- Dual-channel temperature converter with intrinsic safety isolation
- Compatible with THC type input signals (-75mV to +75mV range)
- Comprehensive LED status indication system
- Robust safety features for hazardous area applications
- Easy DIN rail mounting and configuration
- Wide operating temperature and humidity range
- Advanced cold junction compensation capabilities