Shenzhen Hengyo Power Technology Co., Limited
                                                                                                           
Verified Supplier
13 Years
Since 2013
Menu

QUINT-PS/3AC/24DC/10 Phoenix Contact Power Supply 2866705

Price Negotiable
Price: negotiable
MOQ: 1
Delivery Time: In stock
Brand: Phoenix Contact
Product Description

Primary-switched power supply unit QUINT POWER, Pluggable screw connection, SFB Technology (Selective Fuse Breaking), input: 3-phase, output: 24 V DC / 10 A

QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states before errors occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 5 V DC ... 56 V DC are covered.

AC operation
Nominal input voltage range 3x 400 V AC ... 500 V AC
Input voltage range 3x 400 V AC ... 500 V AC -20 % ... +15 %
2x 400 V AC ... 500 V AC -10 % ... +15 %
Input voltage range DC 450 V DC ... 800 V DC
Voltage type of supply voltage AC
Inrush current < 15 A (at 25 °C)
Inrush current integral (I2t) < 1.5 A2s
Inrush current limitation 15 A
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Mains buffering time > 30 ms (400 V AC)
> 46 ms (500 V AC)
Current consumption 3x 1.2 A (400 V AC)
3x 1 A (500 V AC)
2x 1.5 A (400 V AC)
2x 1.3 A (500 V AC)
Nominal power consumption 411 VA
Protective circuit Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi) 0.62
Typical response time < 0.45 s
Permissible backup fuse B6 B10 B16 AC:
Permissible DC backup fuse DC: Connect a suitable fuse upstream
Recommended breaker for input protection 6 A ... 16 A (AC: Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA
DC operation
Nominal input voltage range 500 V DC ... 600 V DC
Input voltage range 500 V DC ... 600 V DC -10 % ... +33 % (mid-point earthed)
Voltage type of supply voltage DC
Current consumption 0.8 A (500 V DC)
0.7 A (600 V DC)
Recommended breaker for input protection 1x 6 A ≥ 1000 V DC (10 x 38 mm, 30 kA L/R = 2 ms)


Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Shenzhen Hengyo Power Technology Co., Limited
Location Room 2407, B Block No.145 Chengshi Zhuchang Bld, Bagua 2nd Rd, Futian Dist. Shenzhen City, China 518029
Contact Person Vivian Chan

Request A Quote

Please check your email address.
Your message must be at least 20 characters.