Phoenix Contact Power Supply 2866789 QUINT-PS/1AC/24DC/40

Price Negotiable
Price: negotiable
MOQ: 1
Delivery Time: In stock
Brand: Phoenix Contact
Product Description

Primary-switched power supply unit QUINT POWER, Screw connection, DIN rail mounting, SFB Technology (Selective Fuse Breaking), input: 1-phase, output: 24 V DC / 40 A

QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states before errors occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 5 V DC ... 56 V DC are covered.

AC operation
Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 85 V AC ... 264 V AC
Derating < 100 V AC (1 %/V)
Input voltage range AC 85 V AC ... 264 V AC
Input voltage range DC 90 V DC ... 300 V DC (UL 508: ≤ 250 V DC)
Electric strength, max. 300 V AC
Voltage type of supply voltage AC
Inrush current < 15 A (typical)
Inrush current integral (I2t) < 1.7 A2s
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Mains buffering time > 35 ms (120 V AC)
> 35 ms (230 V AC)
Current consumption 8.8 A (120 V AC)
4.6 A (230 V AC)
9.5 A (110 V DC)
4.7 A (220 V DC)
Nominal power consumption 1157 VA
Protective circuit Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi) 0.88
Typical response time < 0.7 s
Input fuse 20 A (slow-blow, internal)
Permissible backup fuse B16 B25 AC:
Permissible DC backup fuse DC: Connect a suitable fuse upstream
Recommended breaker for input protection 16 A ... 20 A (AC: Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA
DC operation
Nominal input voltage range 120 V DC ... 300 V DC (UL 508: ≤ 250 V DC)
Input voltage range 90 V DC ... 300 V DC (UL 508: ≤ 250 V DC)
Derating < 120 V DC (0.5 %/V)
Voltage type of supply voltage DC

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Shenzhen Hengyo Power Technology Co., Limited
Location Room 2407, B Block No.145 Chengshi Zhuchang Bld, Bagua 2nd Rd, Futian Dist. Shenzhen City, China 518029
Contact Person Vivian Chan

Request A Quote

Please check your email address.
Your message must be at least 20 characters.