Shenzhen Hengyo Power Technology Co., Limited
                                                                                                           
Verified Supplier
13 Years
Since 2013
Menu

QUINT4-PS/1AC/24DC/40 Phoenix Contact Power Supply 2904603

Price Negotiable
Price: negotiable
MOQ: 1
Delivery Time: In stock
Brand: Phoenix Contact
Product Description

Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB (selective fuse breaking) technology, and NFC interface, input: 1-phase, output: 24 V DC/40 A

The fourth generation of the high-performance QUINT POWER power supplies ensures superior system availability by means of new functions. Signaling thresholds and characteristic curves can be individually adjusted via the NFC interface.
The unique SFB technology and preventive function monitoring of the QUINT POWER power supply increase the availability of your application.

Control input (configurable) Rem Output power ON/OFF (SLEEP MODE)
Default Output power ON (>40 kΩ/24 V DC/open bridge between Rem and SGnd)
AC operation
Network type Star network
Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 100 V AC ... 240 V AC -15 % ... +10 %
Derating < 100 V AC (1 %/V)
Electric strength, max. 300 V AC 60 s
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC
Inrush current typ. 11 A (at 25 °C)
Inrush current integral (I2t) < 0.4 A2s
Inrush current limitation 11 A (after 1 ms)
AC frequency range 50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (fN) 50 Hz ... 60 Hz -10 % ... +10 %
16.7 Hz (acc. to EN 50163)
Mains buffering time typ. 28 ms (120 V AC)
typ. 29 ms (230 V AC)
Current consumption 6.8 A (100 V AC)
5.5 A (120 V AC)
2.8 A (230 V AC)
2.7 A (240 V AC)
Nominal power consumption 520 VA
Protective circuit Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi) 0.98
Switch-on time < 1 s
Typical response time 300 ms (from SLEEP MODE)
Input fuse 12 A (slow-blow, internal)
Recommended breaker for input protection 10 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE < 3.5 mA
1.7 mA (264 V AC, 60 Hz)
DC operation
Nominal input voltage range 110 V DC ... 250 V DC
Input voltage range 110 V DC ... 250 V DC -18 % ... +40 %
Derating < 110 V DC (1 %/V)
Voltage type of supply voltage DC
Current consumption 6 A (110 V DC)
2.5 A (250 V DC)



Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Shenzhen Hengyo Power Technology Co., Limited
Location Room 2407, B Block No.145 Chengshi Zhuchang Bld, Bagua 2nd Rd, Futian Dist. Shenzhen City, China 518029
Contact Person Vivian Chan

Request A Quote

Please check your email address.
Your message must be at least 20 characters.