Ex i repeater power supply and input signal conditioner, HART-transparent. Transmits supplied or active 0/4 … 20 mA signals from the Ex area to a load (active or passive) in the safe area. 3-way electrical isolation, SIL 2 in accordance with IEC 61508, with Push-in connection

Signal: Repeater power supply operation
Description of the input Active current input, intrinsically safe
Number of inputs 1
Input signal Current
Current input signal 4 mA ... 20 mA
Current limitation 25 mA
Transmitter supply voltage > 16 V (20 mA)
> 15.3 V (22.5 mA)
Polarization and surge protection Yes
Underload/overload signal range 0 mA ... 24 mA (Extended transmission range for diagnostics)
Signal: Signal conditioner operation
Description of the input Passive current input, intrinsically safe
Current input signal 0 mA ... 20 mA
4 mA ... 20 mA
Voltage drop < 3.5 V (in input isolating amplifier operation)
Underload/overload signal range 0 mA ... 24 mA (Extended transmission range for diagnostics)

Signal: Repeater power supply operation
Output description Current output (active and passive)
Number of outputs 1
Current output signal 4 mA ... 20 mA (active)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Load/output load current output < 1000 Ω (20 mA)
< 825 Ω (24 mA)
Output ripple < 20 mVrms
Output behavior in the event of an error 0 mA (Cable break in the input)
≥ 22.5 mA (Cable short-circuit in the input)
Underload/overload signal range 0 mA ... 24 mA (Extended transmission range for diagnostics)
Signal: Signal conditioner operation
Output description Current output (active and passive)
Current output signal 0 mA ... 20 mA (active)
4 mA ... 20 mA (active)
0 mA ... 20 mA (14 ... 26 V ext. source voltage)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Load/output load current output < 1000 Ω (20 mA)
< 825 Ω (24 mA)
Output ripple < 20 mVrms
Output behavior in the event of an error 0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)
Underload/overload signal range 0 mA ... 24 mA (Extended transmission range for diagnostics)

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Shenzhen Hengyo Power Technology Co., Limited
Location Room 2407, B Block No.145 Chengshi Zhuchang Bld, Bagua 2nd Rd, Futian Dist. Shenzhen City, China 518029
Contact Person Vivian Chan

Request A Quote

Please check your email address.
Your message must be at least 20 characters.