The MTLx526 enables two separate IS circuits in a hazardous area to be contact controlled by one or two, on/off, control signals in a safe area. Applications include the calibration of strain–gauge bridges; changing the polarity (and thereby the tone) of an IS sounder; the testing of IS fire alarms; and the transfer of safe-area signals into an annunciator with IS input terminals not segregated from each other. The output–relay contacts are certified as non–energy–storing apparatus, and can be connected to any IS circuit without further certification, provided that separate IS circuits are such that they would remain safe if connected together.


SPECIFICATION

See also common specification

Number of channels

Two, fully floating

Location of control circuit

Safe area

Input/output characteristics

Contact/Logic mode

(Inputs suitable for switch contacts, an open–collector transistor or logic drive)


Relay energised if Relay de–energised if Loop powered mode Relay energised if Relay de-energised if < 450Ω or < 1V applied> 5kΩ or > 2V applied (35V max.)
>20V<17V

Power supply failure protection

Relays de–energised if supply fails

Response time

25ms nominal


Contacts (suitable for connection to IS circuits)


1–pole changeover per channel


Contact rating


250V ac, limited to 40V dc for IS applications, 2A (reactive loads must be suppressed)


Contact life expectancy


2 x 107 operations at maximum IS load


Relay drive (see switch setting table)


Choice of "loop-powered" or "contact/logic" control, for both channels, by switch selection. A further switch option ("1in2out") enables either input, in contact/logic mode, to activate both outputs.


LED indicators


Green: power indication


Yellow: two: output status, on when relay energised


Power requirement, Vs


41mA at 20V dc 44mA at 24V dc 60mA at 35V dc


Power dissipation within unit


1.1W maximum at 24V


Safety description (each channel)


Non-energy–storing apparatus: relay contacts may be connected to any IS circuit without further consideration


User switch settings for operating mode


Mode Function SW1 SW2 SW3 SW4
Contact/Logic Input 2 ch Off On On On
1in2out On On On On
Loop Powered 2 ch Off Off Off Off

MTL4526

MTL552 

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Shenzhen Hengyo Power Technology Co., Limited
Location Room 2407, B Block No.145 Chengshi Zhuchang Bld, Bagua 2nd Rd, Futian Dist. Shenzhen City, China 518029
Contact Person Vivian Chan

Request A Quote

Please check your email address.
Your message must be at least 20 characters.