Pepperl+Fuchs KCD2-SOT-1.LB SIL 2 Certified Isolated Safety Barrier with Galvanic Isolation and Configurable Dual Output
The KCD2-SOT-1.LB is a high-performance 1-channel switch amplifier from Pepperl+Fuchs' K-System, specifically engineered to transfer digital signals from field devices to control systems with complete galvanic isolation. This signal conditioner accepts NAMUR sensors (acc. to EN 60947-5-6) or dry contact inputs and provides two passive transistor outputs that can be configured as dual signal outputs or one signal output and one error output.
With a compact 12.5 mm width and 24 V DC power supply (via Power Rail or terminals), the KCD2-SOT-1.LB can be used as a signal splitter (1 input to 2 outputs), making it the ideal solution for applications requiring redundant signal distribution or combined signal and fault monitoring.
Certified for SIL 2 (SC 3) acc. to IEC/EN 61508, the KCD2-SOT-1.LB delivers reliable, safety-rated performance for demanding industrial automation and process control applications.
| Code Segment | Meaning |
|---|---|
| KCD2 | K-System, 2-channel housing width (12.5 mm) |
| SOT | Switch Output — digital signal conditioner |
| -1 | 1-channel |
| .LB | Specific configuration variant with dual output functionality |
The ".LB" suffix denotes the version with configurable second output (signal or fault message), distinguishing it from standard models.
- Signal Splitter Functionality: One input drives two passive transistor outputs — use as a signal splitter for redundant control systems or for driving multiple devices from a single field sensor
- Configurable Second Output: The second output can be configured via DIP switch as either a signal output (duplicating the input signal) or a fault message output (indicating line fault conditions) — providing application flexibility
- Dual Input Compatibility: Accepts both NAMUR sensors (acc. to EN 60947-5-6) and dry contact (mechanical switch) inputs — flexible field device connectivity
- Line Fault Detection (LFD): Monitors field wiring for breakage (I ≤ 0.1 mA) and short-circuit (I ≥ 6.5 mA) conditions — provides diagnostic information for predictive maintenance
- Reversible Mode of Operation: DIP-switch configurable for normally open or normally closed operation — adapts to any application requirement
- Galvanic Isolation: Reinforced insulation (300 Veff) between input/output and input/power supply — ensures safe separation of field and control circuits
- SIL 2 Certified: Safety Integrity Level 2 (SC 3) acc. to IEC/EN 61508 — suitable for safety-related applications
- High Switching Frequency: Operates up to 5 kHz — supports high-speed digital signal processing
- Fast Response Time: ≤ 200 µs response — ensures real-time signal transfer
- Power Rail Compatibility: Connects to Pepperl+Fuchs Power Rail for simplified daisy-chained power distribution
- LED Status Indicators: Visual indication of channel status, fault conditions, and power supply — simplifies troubleshooting
| Parameter | Value |
|---|---|
| Manufacturer | Pepperl+Fuchs SE |
| Product Type | Switch Amplifier / Signal Conditioner |
| Model | KCD2-SOT-1.LB |
| Part Number | 214246 |
| Signal Type | Digital Input |
| Parameter | Value |
|---|---|
| Safety Integrity Level (SIL) | SIL 2 |
| Systematic Capability (SC) | SC 3 |
| Parameter | Value |
|---|---|
| Connection | Power Rail or terminals 9+, 10- |
| Rated Voltage | 19 ... 30 V DC |
| Ripple | ≤ 10 % |
| Rated Current | 20 ... 15 mA |
| Power Dissipation | ≤ 700 mW (including output power) |
| Parameter | Value |
|---|---|
| Connection | terminals 1+, 2- |
| Rated Values | acc. to EN 60947-5-6 (NAMUR) |
| Open Circuit Voltage | approx. 10 V DC |
| Short-Circuit Current | approx. 8 mA |
| Switching Point | 1.2 ... 2.1 mA |
| Switching Hysteresis | approx. 0.2 mA |
| Line Fault Detection - Breakage | I ≤ 0.1 mA |
| Line Fault Detection - Short-Circuit | I ≥ 6.5 mA |
| Minimum Pulse/Pause Ratio | 100 µs / 100 µs |
| Parameter | Value |
|---|---|
| Connection | Output I: terminals 5, 6 ; Output II: terminals 7, 8 |
| Output Type | 2 x passive transistor |
| Rated Voltage | 30 V DC |
| Rated Current | 50 mA |
| Response Time | ≤ 200 µs |
| Signal Level - 1-signal | (external voltage) - 3 V max. for 50 mA |
| Signal Level - 0-signal | blocked output (off-state current ≤ 10 µA) |
| Output I Function | Signal output |
| Output II Function | Configurable: Signal output or fault message output |
| Collective Error Message | Power Rail |
| Parameter | Value |
|---|---|
| Switching Frequency | ≤ 5 kHz |
| Parameter | Value |
|---|---|
| Input/Output | reinforced insulation, 300 Veff (EN 50178) |
| Input/Power Supply | reinforced insulation, 300 Veff (EN 50178) |
| Output/Power Supply | basic insulation, 50 Veff (EN 50178) |
| Output/Output | basic insulation, 50 Veff (EN 50178) |
| Parameter | Value |
|---|---|
| Display Elements | LEDs (acc. to NAMUR NE44) |
| Control Elements | DIP switch |
| Configuration | via DIP switches |
| Labeling | space for labeling at the front |
| Parameter | Value |
|---|---|
| Ambient Temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Extended Temperature Range | up to 70 °C (158 °F) with proper mounting conditions |
| Parameter | Value |
|---|---|
| Degree of Protection | IP20 |
| Connection | Screw terminals |
| Mass | approx. 100 g |
| Dimensions (W x H x D) | 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) |
| Housing Type | A2 |
| Mounting | 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Standard | Compliance |
|---|---|
| EMC Directive | 2014/30/EU |
| EMC Standard | EN 61326-1:2013 (industrial locations) |
| NAMUR | NE 21:2011, NE44 |
| Input Standard | EN 60947-5-6:2000 |
| Protection | IEC 60529:2001 |
| Electrical Shock Protection | IEC 61010-1:2010 |
The KCD2-SOT-1.LB provides complete galvanic isolation between field circuits and control circuits. The device transfers digital signals from NAMUR sensors (proximity sensors, level switches, flow monitors) or dry contacts (mechanical switches, relays, push buttons) from the field to the control system.
- The input signal controls two passive transistor outputs independently
- Output I always provides the signal output (following the input state)
- Output II can be configured via DIP switch as either:
- Signal output: Duplicates the input signal (signal splitter mode)
- Fault message output: Indicates line fault conditions (breakage or short-circuit)
- The mode of operation can be reversed via DIP switches (normally open / normally closed)
- Line fault detection (LFD) monitors field wiring integrity and can be disabled if not required
- Fault conditions are indicated via front-panel LEDs according to NAMUR NE44 and a collective error message output on the Power Rail
The KCD2-SOT-1.LB is specifically designed for digital signal transfer and distribution in demanding industrial environments:
| Industry | Application |
|---|---|
| Process Control | Signal splitting for redundant PLC/DCS input configurations |
| Oil & Gas | Distribution of NAMUR proximity sensor signals to multiple control systems |
| Chemical Processing | Combined signal and fault monitoring for critical safety circuits |
| Pharmaceutical | SIL 2 certified signal transfer for safety-related applications with diagnostic feedback |
| Factory Automation | High-speed (5 kHz) digital signal processing with redundant output distribution |
| Water/Wastewater | Pump status monitoring with separate signal and fault reporting |
- NAMUR inductive proximity sensors (EN 60947-5-6)
- NAMUR capacitive level switches
- Mechanical dry contacts (push buttons, limit switches, relays)
- Intrinsically safe sensors via Zener barriers
- Signal Splitter Mode: One sensor feeding two PLC input cards (redundant architecture)
- Signal + Fault Mode: One output to control system, second output to alarm panel for fault notification
Built-in Signal Splitter — Unlike standard switch amplifiers, the KCD2-SOT-1.LB provides two configurable outputs from a single input, eliminating the need for external signal splitters and reducing panel space requirements.
Combined Signal and Fault Monitoring — The ability to configure Output II as a fault message output provides a dedicated diagnostic channel, enabling predictive maintenance and faster fault response without consuming additional control system inputs for status monitoring.
SIL 2 Certified for Safety Applications — Certified acc. to IEC/EN 61508 with Systematic Capability SC 3, the KCD2-SOT-1.LB is suitable for use in safety instrumented systems (SIS) up to SIL 2.
Space-Saving Design — At just 12.5 mm width (housing type A2), the KCD2-SOT-1.LB provides a complete signal splitting solution in a compact footprint, maximizing DIN rail density.
Built-in Diagnostics — Line fault detection (LFD) continuously monitors field wiring for breakage and short-circuit conditions, enabling predictive maintenance and reducing unplanned downtime.
Flexible Configuration — DIP-switch configurable for mode of operation (NO/NC), LFD on/off, and Output II function — adapts to any application without external programming tools.
Proven Pepperl+Fuchs K-System — The K-System is the industry standard for signal conditioning and isolation, trusted globally for reliability, quality, and long service life.
| Model | Channels | Outputs | Output II Function | Primary Application |
|---|---|---|---|---|
| KCD2-SOT-1.LB | 1 | 2 x passive transistor | Configurable (signal or fault) | Signal splitting + fault monitoring |
| KCD2-SOT-2 | 2 | 2 x passive transistor | N/A (independent channels) | Two independent sensors to PLC |
| KCD2-SOT-1 | 1 | 1 x passive transistor | N/A | Standard single output |
| KCD2-SOT-1.SP | 1 | 1 x passive transistor | N/A | Spring terminal version |
| KCD2-SOT-2.LB | 2 | 4 x passive transistor | Configurable per channel | Dual signal splitting |
| Item | Details |
|---|---|
| Part Number | KCD2-SOT-1.LB |
| Manufacturer Part Number | 214246 |
| Brand | Pepperl+Fuchs SE |
| Product Family | K-System |
| Country of Origin | Germany |
| Condition | New, Original, Factory Sealed |
| Minimum Order Quantity | 1 piece |
| Warranty | Manufacturer's standard warranty |
| Shipping | Immediate dispatch via DHL, FedEx, UPS, TNT |
Contact our sales team for volume pricing, datasheet downloads, or technical application support.
| Certification | Status | Details |
|---|---|---|
| SIL 2 | ✅ Certified | IEC/EN 61508, SC 3 |
| CE | ✅ Compliant | EMC Directive 2014/30/EU |
| NAMUR | ✅ Compliant | NE 21:2011, NE44 |
| RoHS | ✅ Compliant | Lead-free |
| cULus | ✅ Listed | UL approval for North America |
| CCC | ✅ Certified | China Compulsory Certification |
| Model | Function | Description |
|---|---|---|
| KCD2-SOT-2.LB | Switch Amplifier | 2-channel, configurable second output per channel |
| KCD2-SOT-1 | Switch Amplifier | Single output version |
| KCD2-SOT-1.SP | Switch Amplifier | Spring terminal version |
| KCD2-STC-1 | SMART Transmitter Conveyor | 4...20 mA input to 4...20 mA output |
| KCD2-SR-2 | Switch Amplifier | 2-channel, relay outputs |
| Power Rail | Accessory | Daisy-chain power distribution for K-System modules |
Get in Touch