Pepperl+Fuchs KFU8-UFC-1.D Frequency Converter, 0.001-10kHz NAMUR Input 4-20mA Analog Output 2 Relay SIL2 for Industrial Automation

Price Negotiable
Price: negotiable
MOQ: 1
Delivery Time: In stock
Brand: PEPPERL+FUCHS
Product Description
Pepperl+Fuchs KFU8-UFC-1.D Frequency Converter
This 1-channel universal frequency converter and signal conditioner converts digital frequency input signals into proportional analog output signals (0/4-20 mA) while functioning as a switch amplifier and trip alarm device.
Product Overview
The Pepperl+Fuchs KFU8-UFC-1.D accepts inputs from NAMUR sensors (acc. to EN 60947-5-6), 2/3-wire sensors, or dry contacts, with frequency measurement from 0.001 Hz to 12 kHz. It features four independent outputs (2 relay + 1 transistor + 1 analog) for exceptional flexibility in industrial automation and process control applications.
Note: A successor product is available. Please verify stock availability before ordering.
Technical Specifications
Model KFU8-UFC-1.D
Input Types NAMUR (EN 60947-5-6), 2/3-wire sensor, dry contact
Input Frequency 0.001 Hz ... 12 kHz
Output I, II Relay (Form C), 250V AC/2A, 40V DC/2A
Output III Electronic/Transistor output, passive, 40V DC/50mA
Output IV Analog output, 0/4-20 mA, load ≤ 650 Ω
Supply Voltage 20-90V DC / 48-253V AC (50-60 Hz)
Safety Rating SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511
Accuracy 0.1% of measured value
Ambient Temperature -20°C ~ 60°C (-4°F ~ 140°F)
Mounting 35mm DIN rail acc. to EN 60715
Key Features
  • Universal frequency converter with wide input range (0.001 Hz to 12 kHz)
  • High accuracy of 0.1% for precise frequency monitoring
  • Four versatile outputs: 2 relay, 1 transistor, and 1 analog
  • Flexible input options for NAMUR, 2/3-wire sensors, and dry contacts
  • Line fault detection for wire breakage and short-circuit monitoring
  • Start-up override function (1-1000 seconds) prevents false alarms
  • Universal power supply compatible with global systems
  • SIL 2 functional safety certification
  • Easy configuration via keypad display or PACTware software
  • Reinforced galvanic isolation for signal integrity and safety
Applications
Process Automation Frequency monitoring from flow meters, speed sensors
Factory Automation Conveyor speed monitoring, RPM measurement
Machine Building Frequency-to-current conversion for PLC inputs
Pump & Motor Control Speed feedback and trip alarm monitoring
Water/Wastewater Flow rate monitoring from frequency-output sensors
Energy Management Frequency monitoring from generators and turbines
Safety Systems SIL2-rated frequency monitoring for safety functions
Certifications & Compliance
SIL 2 IEC/EN 61508 / IEC/EN 61511 Functional Safety Assessment by exida
CE 2014/30/EU, 2014/35/EU EMC & Low Voltage Directives
UKCA UK Conformity Assessed
RoHS Compliant - Environmentally friendly
Ordering Information
Manufacturer: Pepperl+Fuchs SE
Part Number: KFU8-UFC-1.D (Alternative: 231195)
Product Status: Active - Successor available
Country of Origin: Germany

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Shenzhen Hengyo Power Technology Co., Limited
Location Room 2407, B Block No.145 Chengshi Zhuchang Bld, Bagua 2nd Rd, Futian Dist. Shenzhen City, China 518029
Contact Person Vivian Chan

Request A Quote

Please check your email address.
Your message must be at least 20 characters.