Shenzhen Hengyo Power Technology Co., Limited
                                                                                                           
Verified Supplier
13 Years
Since 2013
Menu

Pepperl+Fuchs KFU8-SR-Ex2.W ATEX Isolated Barrier 2-Channel Relay Output Ex ia Input for Hazardous Area

Price Negotiable
Price: negotiable
MOQ: 1
Delivery Time: In stock
Brand: PEPPERL+FUCHS
Product Description
Product Overview
The Pepperl+Fuchs KFU8-SR-Ex2.W is a 2-channel isolated barrier switch amplifier from the K-System, designed for intrinsic safety applications in hazardous areas. It transfers digital signals from NAMUR sensors or dry contact mechanical switches from the hazardous area to the safe area with relay contact output.
This device features line fault detection (LFD) for monitoring field circuit breakage and short-circuit conditions, and supports SIL 2 (SC 3) functional safety rating according to IEC/EN 61508, making it ideal for safety-critical applications.
Universal Power Supply: Operates on either 19-30V DC or 90-253V AC (50-60Hz), providing global compatibility with any control system without the need for a separate DC power supply.
Key Specifications
Model KFU8-SR-Ex2.W
Brand Pepperl+Fuchs
Product Type Switch Amplifier / 2-Channel Isolated Barrier
Signal Type Digital Input
Input Types NAMUR (acc. to EN 60947-5-6) or Dry Contact
Output Relay Contact Output (Form C changeover, 2 channels)
Supply Voltage 19-30V DC / 90-253V AC 50-60Hz
Safety Rating SIL 2 (SC 3) acc. to IEC/EN 61508
Line Fault Detection (LFD) Yes (breakage ≤0.1mA, short-circuit >6mA)
Switching Frequency ≤ 10 Hz
Contact Loading 250V AC/2A, 126.5V AC/4A, 40V DC/2A resistive load
Ambient Temperature -40°C to 60°C (extendable to 70°C with proper mounting)
Protection Rating IP20
Dimensions (WxHxD) 20 x 119 x 115 mm (B2 housing)
Mounting 35mm DIN rail acc. to EN 60715
Weight approx. 150 g
Certifications ATEX, IECEx, UL, SIL2, CCC Ex, DNV Marine
Part Status Active / Current Model
Key Features
2-Channel Isolated Barrier
  • Two independent input/output channels in a single 20mm wide housing — saves cabinet space
  • Each channel provides galvanic isolation between field and control circuits
Universal Power Supply
  • Wide-range input: 19-30V DC OR 90-253V AC (50-60Hz)
  • Eliminates the need for separate DC power supplies
  • Compatible with global power systems — works anywhere in the world
SIL 2 Functional Safety
  • SIL 2 (SC 3) certified according to IEC/EN 61508
  • TUV Rheinland Functional Safety Certificate: 968/FSP 2319.00/22
  • Suitable for safety-related applications in process industries
Line Fault Detection (LFD)
  • Monitors field circuit for wire breakage (I ≤ 0.1 mA) and short-circuit (I > 6 mA)
  • Provides diagnostic indication for preventive maintenance
  • Fault relay output for remote error indication
Flexible Input Options
  • Accepts NAMUR sensors (acc. to EN 60947-5-6) or dry contact mechanical switches
  • Open circuit voltage: approx. 8V DC / short-circuit current: approx. 8mA
  • Switching point: 1.2 ... 2.1 mA, hysteresis approx. 0.2 mA
Relay Output
  • Form C changeover relay contacts for versatile load switching
  • Mechanical life: 10⁷ switching cycles
  • Energized/De-energized delay: approx. 20 ms
Reinforced Galvanic Isolation
  • Reinforced insulation between input/output, input/power supply, output/power supply, and output/output
  • Rated insulation voltage: 300 Veff acc. to IEC/EN 61010-1
  • Safe electrical isolation acc. to IEC/EN 60079-11 (375V peak)
Easy Configuration
  • DIP switch configuration for easy setup — no software required
  • Space for labeling at the front for clear identification
  • LED indicators for operating status and fault conditions per NAMUR NE44
DIP Switch Configuration
Switch Function
S1 Reverses normal output state (energized ↔ de-energized)
S2 Reverses output state for second channel
S3 Enables/disables Line Fault Detection (LFD)
Refer to the instruction manual for detailed configuration guidance.
Function Description
This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area.
The proximity sensor or switch controls a form C changeover relay contact for the safe area load. The normal output state can be reversed using switches S1 and S2. Switch S3 is used to enable or disable line fault detection of the field circuit.
During an error condition, the relays revert to their de-energized state and the LEDs indicate the fault according to NAMUR NE44.
Applications
Industry Application Examples
Oil & Gas Level monitoring, flow control, valve position feedback in hazardous areas
Chemical / Pharmaceutical Tank level measurement, reactor monitoring, process control
Power Generation Turbine monitoring, boiler control, coal handling systems
Mining Conveyor monitoring, equipment control in explosive atmospheres
Water/Wastewater Pump control, level switching in potentially explosive environments
Food & Beverage Process monitoring in solvent-handling areas
Typical Use Cases:
  • Intrinsic safety barriers for hazardous area sensors
  • NAMUR proximity sensor interfacing
  • Mechanical switch signal transfer from Zone 0/1/2 areas
  • Functional safety systems requiring SIL 2 rating
  • Remote status monitoring and fault detection
Wiring Connections
Terminal Function
1+, 2+, 3- Channel 1: Field side input (NAMUR or dry contact)
4+, 5+, 6- Channel 2: Field side input (NAMUR or dry contact)
7, 8, 9 Output I: Signal relay (Form C changeover)
10, 11, 12 Output II: Signal relay (Form C changeover)
14, 15 Power supply: 19-30V DC or 90-253V AC
Certifications & Compliance
ATEX: FIDI 22 ATEX 0029X — II 3(1)G Ex ec nC [ia Ga] IIC T4 Gc
IECEx: IECEx FIDI 22.0003X — Ex ec nC [ia Ga] IIC T4 Gc
SIL 2: 968/FSP 2319.00/22 — TUV Rheinland Functional Safety
UL/cULus: E106378 — Hazardous Locations
CCC Ex: 2023322316005169 — China
DNV Marine: TAA00001WX — Marine applications
RoHS: Compliant — Environmentally friendly
CE: DOC-6610 — EU Directives
Environmental & Mechanical Specifications
Operating Temperature -40°C to 60°C (-40°F to 140°F)
Extended Temperature Up to 70°C (158°F) with proper mounting
Protection Rating IP20
Mounting 35mm DIN rail acc. to EN 60715
Housing Type B2 (20mm width)
Connection Screw terminals
Vibration Resistance 2g (according to IEC 60068-2-6)
Ordering Information
Manufacturer Pepperl+Fuchs SE
Part Number KFU8-SR-Ex2.W
Product Status Active / Current Model
List Price $340.00 USD (reference)
Country of Origin Germany / Singapore
Packaging Factory sealed box
GTIN 4050143515226
Recommended Accessories
Accessory Model Description
Terminal Block KF-ST-5GN 3-pin screw terminal, green, 5 pieces
Terminal Block KF-ST-5BU 3-pin screw terminal, blue, 5 pieces
Coding Pins KF-CP For terminal block coding, 20 x 6 pins
Key Benefits
Enhanced Safety
SIL2 certification and Ex ia input protection for hazardous areas
Global Compatibility
Universal AC/DC power supply works anywhere in the world
Reduced Downtime
Line fault detection enables predictive maintenance
Space Saving
2 channels in a 20mm wide housing maximizes cabinet density
Easy Commissioning
DIP switch configuration eliminates software tools
Proven Reliability
Pepperl+Fuchs K-System trusted in industrial safety worldwide
Comprehensive Certifications
ATEX, IECEx, UL, SIL2, CCC Ex, DNV — one product for global use
Wide Temperature Range
-40°C to 70°C for harsh environments
Fast Response
10 Hz switching frequency with 20 ms delay times
Need support? Contact us for:
  • Technical specifications and complete datasheets
  • Volume pricing and availability
  • Installation and wiring guidance
  • Functional safety documentation
  • Application engineering support

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Shenzhen Hengyo Power Technology Co., Limited
Location Room 2407, B Block No.145 Chengshi Zhuchang Bld, Bagua 2nd Rd, Futian Dist. Shenzhen City, China 518029
Contact Person Vivian Chan

Request A Quote

Please check your email address.
Your message must be at least 20 characters.