ABB 1SFA898116R7000 Softstarter PSTX60-600-70 Has A Rated Max Operational Current Of 60A
Price:
Negotiable
MOQ:
1
Delivery Time:
5-8DAYS
Brand:
ABB
Product Description
ABB PSTX60-600-70 Softstarter
The ABB 1SFA898116R7000 PSTX60-600-70 softstarter delivers reliable motor control with a rated maximum operational current of 60 A and operating voltage range from 208-600 V AC.
Ordering Information
Minimum Order Quantity:
1 piece
Customs Tariff Number:
85371091
Technical Documentation
Data Sheet & Technical Information:
Softstarter main catalog
Quick Start Guide:
PSTX quick start guide
Installation Manual:
PSTX - Installation and commissioning manual
Technical Handbook:
Softstarter Handbook
CAD Files:
2D and 3D files for CAD systems
EPLAN Data:
EPLAN EDZ PSTX470
Physical Dimensions
| Dimension | Value |
|---|---|
| Width | 361 mm |
| Height | 493 mm |
| Depth/Length | 282 mm |
| Weight | 25 kg |
Electrical Specifications
| Parameter | Specification |
|---|---|
| Rated Operational Voltage | 208 ... 600 V AC |
| Rated Control Supply Voltage (Us) | 100 ... 250 V AC |
| Rated Control Circuit Voltage (Uc) | 24 V DC |
| Rated Frequency (f) | 50/60 Hz |
| Rated Operational Current - In-Line Connection (Ie) | 470 A |
| Rated Operational Current - Inside Delta Connection | 814 A |
Power Ratings
In-Line Connection
| Voltage | Power Rating |
|---|---|
| 230 V | 132 kW |
| 400 V | 250 kW |
| 500 V | 315 kW |
Inside Delta Connection
| Voltage | Power Rating |
|---|---|
| 230 V | 250 kW |
| 400 V | 450 kW |
| 500 V | 600 kW |
Operational Features
Service Factor
100%
Overload Protection
Built-in electronic overload protection
Integrated Electronic Overload
Yes
Starting Capacity
4xIe for 10s
Ramp Time
1 ... 120 seconds
Initial Voltage During Start
10 ... 99%
Step Down Voltage Special Ramp
100 ... 10%
Control & Signaling
Switch for Inside Delta Connection
Yes
Run Signal Relay
Yes
By-pass Signal Relay
Yes
Fault Signal Relay
Yes
Overload Signal Relay
Yes
LED Status Indicators
| Indicator | Color | Status |
|---|---|---|
| Ready to Start/Standby | Green | ON |
| Running | Green | R |
| Protection | Yellow | Active |
| Fault | Red | Active |
Communication Protocols
Modbus-RTU; Modbus-TCP; Ethernet-IP; EtherCAT; DeviceNet; CANopen; Profibus; Profinet; BACnet-IP; BACnet-MSTP
Protection & Safety
Degree of Protection
IP00 (Main Terminals) acc. to IEC 60529, IEC 60947-1, EN 60529
Key Functions
- Auto phase sequence detection
- Automatic restart
- Current limit
- Current limit ramp
- Dual current limit
- Dynamic brake
- Electricity metering
- Electronic overload Time-to-cool
- Emergency mode
- Event log
Protection Functions
- Bypass open protection
- Current imbalance protection
- Current underload protection
- Dual overload (separate overload for start and run)
- Earth fault protection / ground fault protection
- Electronic overload protection, EOL
- Extension IO failure protection
- Fieldbus failure protection
- HMI failure protection
- Locked rotor protection
- Max number of starts/hour
- Over voltage protection
- Phase reversal protection
- Power factor underload protection
- PT-100 connection
- PTC connection
- Too long current limit protection
- Too long start time protection
- Under voltage protection
- User defined protection
- Voltage imbalance protection
Warning System
- Current imbalance warning
- Current underload warning
- Electronic overload Time-to-trip
- EOL warning
- Faulty fan warning
- Locked rotor warning
- Motor runtime limit warning
- Over voltage warning
- Phase loss warning (for standby)
- Power factor underload warning
- Short circuit warning (for Limp mode)
- THD(U) - Total Harmonic Distortion warning
- Thyristor overload warning (SCR)
- Under voltage warning
- Voltage imbalance warning
Related Videos
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.
Company
Shaanxi Qindiyuan Environmental Protection Equipment Co., Ltd.
Location
F1-803, Guorun Silu Jin Rong Zhongxin, Qindu District, Xianyang City, Shaanxi Province
Contact Person
Leon Lee