ABB 1SFA898111R7000 softstarter PSTX170-600-70 has a rated maximum operational current of 170 A with an operating voltage span from 208...600 V A
Price:
Negotiable
MOQ:
1
Delivery Time:
5-8days
Brand:
ABB
Product Description
ABB PSTX170-600-70 Softstarter
The ABB 1SFA898111R7000 PSTX170-600-70 softstarter delivers reliable motor control with a rated maximum operational current of 170 A and operating voltage range from 208-600 V AC.
Ordering Information
Minimum Order Quantity:
1 piece
Customs Tariff Number:
85371091
Technical Documentation
Data Sheet & Technical Information:
Softstarter main catalog
Quick Start Guide:
PSTX quick start guide
Installation Manual:
PSTX - Installation and commissioning manual
Handbook:
Softstarter Handbook
CAD Files:
2D and 3D files for CAD systems
EPLAN Data:
EPLAN EDZ PSTX170
Physical Dimensions
| Dimension | Value |
|---|---|
| Width | 199 mm |
| Height | 377 mm |
| Depth/Length | 283.3 mm |
| Weight | 8.9 kg |
Electrical Specifications
| Parameter | Value |
|---|---|
| Rated Operational Voltage | 208 ... 600 V AC |
| Rated Control Supply Voltage (Us) | 100 ... 250 V AC |
| Rated Control Circuit Voltage (Uc) | 24 V DC |
| Rated Frequency (f) | 50/60 Hz |
| Rated Operational Current - In-Line | 170 A |
| Rated Operational Current - Inside Delta | 300 A |
Power Ratings - In-Line Connection
| Voltage | Power |
|---|---|
| 230 V | 45 kW |
| 400 V | 90 kW |
| 500 V | 110 kW |
Power Ratings - Inside Delta Connection
| Voltage | Power |
|---|---|
| 230 V | 90 kW |
| 400 V | 160 kW |
| 500 V | 200 kW |
Control & Protection Features
Starting & Control Parameters
Starting Capacity
4xIe for 10s
Ramp Time
1 ... 120 seconds
Initial Voltage
10 ... 99 %
Current Limit
1.5 ... 7.5 xIe
Integrated Protection
Built-in electronic overload protection with overload signal relay
Signal Relays
Run Signal
Yes
By-pass Signal
Yes
Fault Signal
Yes
Communication & Connectivity
Modbus-RTU; Modbus-TCP; Ethernet-IP; EtherCAT; DeviceNet; CANopen; Profibus; Profinet; BACnet-IP; BACnet-MSTP
Environmental Specifications
| Condition | Temperature Range |
|---|---|
| Operation | -25 ... +60 °C |
| Storage | -40 ... +70 °C |
UL/CSA Ratings
| Voltage Range | Horsepower Rating |
|---|---|
| 200 ... 208 V AC | 50 Hp |
| 220 ... 240 V AC | 60 Hp |
| 440 ... 480 V AC | 125 Hp |
| 550 ... 600 V AC | 150 Hp |
Related Videos
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.
Company
Shaanxi Qindiyuan Environmental Protection Equipment Co., Ltd.
Location
F1-803, Guorun Silu Jin Rong Zhongxin, Qindu District, Xianyang City, Shaanxi Province
Contact Person
Leon Lee