Schneider LRD08C Protection And Control Components Thermal Overload Relay
Price:
Negotiable
MOQ:
1 pcs
Delivery Time:
5-7 days
Brand:
Schneider
Product Description
Schneider LRD08C Thermal Overload Relay
Professional three-phase motor protection relay with adjustable current settings and comprehensive safety features.
Core Specifications
Essential technical parameters for engineering and procurement:
| Parameter | Specification |
|---|---|
| Brand / Model | Schneider Electric LRD08C |
| Product Series | TeSys D (Deca) Thermal Overload Relay |
| Setting Current Range | 2.5–4A (Adjustable with white knob) |
| Trip Class | Class 10A (Fast trip, approximately 7.2s operation time for 1.5 times current) |
| Number of Poles | 3P (Three-phase protection) |
| Auxiliary Contacts | 1NO + 1NC (95-96 normally closed, 97-98 normally open) |
| Contact Capacity | 4A / 690V AC |
| Installation Method | Directly mounted below LC1-D09~D38 contactors; independent DIN rail (TH35) mounting |
| Reset Method | Manual (H) / Automatic (A) optional (blue reset button) |
| Physical Dimensions | 45 (width) * 66 (D) * 70 (H) mm |
| Net Weight / Gross Weight | Approx. 0.18 kg / Approx. 0.22 kg |
| Protection Rating | IP20 (for use in control cabinets) |
| Operating Temperature | -20℃~+60℃ (wide temperature range) |
| Storage Temperature | -40℃~+85℃ |
| Certifications | CE, UL 61010, CSA, RoHS, Green Premium |
| Country of Origin | France |
Logistics and Customs Information
Dangerous Goods Attributes:
None (general cargo)
Customs Code (HS):
8536300000 (thermal overload relay for motor protection)
Packaging Specifications:
Original cardboard box, volume approximately 0.00021 m³
Customs Declaration:
Schneider Electric TeSys D Thermal Overload Relay, 3-Pole, 2.5–4A Adjustable, Class 10A, 1NO+1NC Auxiliary Contacts
Core Protection Features
Advanced Motor Protection
- Differential Bimetallic Strip: Accurately detects three-phase current imbalance and overload with temperature compensation for stable protection across wide temperature ranges
- Class 10A Fast Tripping: No tripping within 1.05×Ir for 2h; tripping within 1.2×Ir for 2h; approximately 7.2s tripping at 1.5×Ir for rapid motor winding protection
- Phase Loss Protection: Quick trip response when any phase current becomes abnormal, preventing motor burnout due to phase loss
- Test/Indication System: Built-in test button and trip indicator (T) for fault simulation and circuit verification
- Security Features: Front cover with lead seal hook to prevent accidental parameter adjustment
Operation Panel Layout
| Component | Function |
|---|---|
| White scale knob | Setting current Ir (2.5–4A) |
| Toggle window | Test button + Trip indicator (T) |
| Red button | Stop (Forced disconnect 95-96) |
| Blue button | Reset (Manual reset) |
| H/A switch | Manual/automatic reset selection |
| Lead seal hook | Lock setting parameters |
Related Videos
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.
Company
Shaanxi Qindiyuan Environmental Protection Equipment Co., Ltd.
Location
F1-803, Guorun Silu Jin Rong Zhongxin, Qindu District, Xianyang City, Shaanxi Province
Contact Person
Leon Lee