Schneider Electric LRD32C Thermal Overload Relay With Class 10A Fast Tripping
Price:
Negotiable
MOQ:
1 pcs
Delivery Time:
5-7 days
Brand:
Schneider
Product Description
Schneider LRD32C Thermal Overload Relay
Core Specifications
| Item | Parameters |
|---|---|
| Brand / Model | Schneider Electric LRD32C (TeSys D Series) |
| Product Type | 3-Pole Differential Thermal Overload Relay |
| Setting Current Range | 23-32A (Adjustable with white knob) |
| Trip Class | Class 10A (Fast tripping, approximately 7.2s operation) |
| Auxiliary Contacts | 1NO + 1NC (95-96 Normally Closed, 97-98 Normally Open) |
| Contact Capacity | 5A / 690V AC |
| Installation Method | Direct mounting below LC1-D25~D38 contactors; DIN rail (TH35) |
| Reset Method | Manual (H) / Automatic (A) optional |
| Physical Dimensions | 45 (W) * 66 (D) * 70 (H) mm |
| Net Weight / Gross Weight | Approx. 0.18 kg / 0.22 kg |
| Protection Rating | IP20 (for indoor control cabinets) |
| Operating Temperature | -20℃ to +60℃ |
| Storage Temperature | -40℃ to +85℃ |
| Certifications | CE, UL 61010, CSA, RoHS, Green Premium |
| Country of Origin | France |
Logistics and Customs Information
- Dangerous Goods: None (general cargo)
- Customs Code (HS): 8536300000
- Packaging: Original cardboard box, 1 unit/box, 33 units/carton
- Unit Volume: Approximately 0.00021 m³
Core Protection Functions
- Differential Bimetallic Strip: Detects three-phase current imbalance and overload with temperature compensation
- Class 10A Fast Tripping: Quick protection for motor windings (approx. 7.2s at 1.5*Ir)
- Phase Loss Protection: Prevents motor burnout from phase current abnormalities
- Test/Indication: Built-in test button and trip indicator for circuit verification
- Lead Seal Lock: Prevents accidental parameter adjustments
Operation Panel Layout
| Component | Function |
|---|---|
| White scale knob | Setting current Ir (23-32A) |
| Toggle window | Test button + Trip indicator (T) |
| Red button | Stop (Forced disconnect 95-96) |
| Blue button | Reset (Manual reset) |
| H/A switch | Manual/automatic reset selection |
| Lead seal hook | Lock setting parameters |
Related Videos