Boiler NOx Nitrogen Oxide CO Oxygen Online Gas Monitoring System
System Overview

Advanced online gas monitoring system designed for boiler applications, providing continuous real-time measurement of NOx, nitrogen oxide, CO, and oxygen levels with exceptional accuracy and reliability.

Key Features
  • Multi-point transmitter functionality for comprehensive data integration, analysis, reporting, and publishing
  • Rapid response time with T90 as quick as 10 seconds
  • Integrated passive relay contact output with audible/visual alarm capabilities
  • Specialized anti-interference sensor design prevents sensor poisoning and damage
  • Advanced front-end pretreatment system with drying and filtration for enhanced accuracy and sensor longevity
  • Comprehensive historical data storage with accessible alarm records
  • Standard HJ212 protocol compatibility for seamless environmental protection platform integration
Technical Specifications
Parameter Specification
Detection Gases NO, CO, NOx, O₂, temperature
Detection Principle Constant potential electrolysis method (imported sensor)
Detection Method Fixed pump suction online continuous monitoring
Measurement Range NO, CO, NOx: 0-500 mg/m³; O₂: 0-25% VOL (optional; custom ranges available)
Resolution 0.01, 0.1
Indication Error ≤±3.0% F.S. (sensor dependent)
Installation Options Wall-mounted, floor-standing, pole-mounted
Repeatability ≤±0.5% F.S.
Zero Drift ≤±5% F.S./year
Range Drift ≤±5% F.S./year
Response Time ≤15S T90
Recovery Time ≤20S
Alarm System Audible and visual alarm, 1 or 2 dry contact signal outputs, adjustable threshold
Protection Level Main body IP54, detector IP66
Operating Temperature -20℃ to +200℃
Operating Humidity ≤95%RH
Relative Humidity 10-95%RH with full temperature and humidity compensation
Power Supply 220V AC, 40W
Working Pressure ≤200Kpa
Data Storage Built-in storage capacity, optional storage card

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Nanjing Juge Environmental Technology Co., Ltd.
Location Building 17, No. 99 Guangli Road, Moling Subdistrict, Jiangning District, Nanjing, Jiangsu
Contact Person Leon Chen

Request A Quote

Please check your email address.
Your message must be at least 20 characters.