OPzS420-2 Tubular Plate Flooded Lead-Acid Battery (For Substation Backup Power)


I. Core Specifications


  • Model: OPzS420-2
  • Rated Voltage: 2V
  • Rated Capacity: 420Ah (C10, 25℃)
  • Battery Type: Tubular Plate Flooded Lead-Acid Battery (OPzS)
  • Design Float Life: 20 years (at 25℃)
  • Maintenance Feature: Low maintenance design, electrolyte replenishment cycle ≥ 3 years

II. Key Advantages


  1. Extreme Environmental Adaptability

    Wide operating temperature range: -40~65℃, ensuring stable performance in harsh substation environments.
  2. High Safety & Low Maintenance

    Acid-proof and explosion-proof design, meeting DIN40736 and other international standards. Long electrolyte replenishment cycle greatly reduces on-site maintenance workload.
  3. Excellent Cycle & Deep Discharge Performance

    Designed for both deep and shallow cycle applications. Achieves 3000 cycles at 50% DOD, with excellent deep discharge resistance and recovery capability, fully meeting the long-term standby and frequent operation needs of substations.
  4. High Compatibility & Stability

    Standard 2V cell design, which can be flexibly assembled into 110V/220V DC power packs to match substation control and protection systems. Features low internal resistance and stable high-current discharge performance.

III. Applications


  • DC operating power supply for substations (for control, protection, signaling, and circuit breaker operation)
  • Backup power for power monitoring and relay protection systems
  • Energy storage systems for telecommunications base stations, solar and wind power
  • UPS/EPS emergency power supply systems

IV. Usage Guidelines


  • Charging Requirements: Float charge voltage: 2.25–2.30V/cell; equalizing charge voltage: 2.35–2.40V/cell. Avoid overcharging or undercharging.
  • Discharging Requirements: Keep daily discharge depth ≤ 50%. 100% full discharge is strictly prohibited to prevent irreversible damage to the battery.
  • Environmental Requirements: Install in a well-ventilated, dry, and dust-free area. Avoid direct sunlight and high humidity. Operating temperature range: -40~65℃, with an optimal operating temperature of 25℃.
  • Maintenance Notes: Regularly check the electrolyte level and cell voltage. Replenish electrolyte every 3 years or as needed.

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company JYC Battery Manufacturer Co., Ltd.
Location Building 2, No. 34, Xialiang Shakenghe Road, Baiyun District, Guangzhou, China
Contact Person joyce

Request A Quote

Please check your email address.
Your message must be at least 20 characters.