KYN18-12 Series High Voltage Switchgear Indoor Removable AC Enclosed Electrical Switchgear
The KYN18-12 Indoor AC Armoured Removable AC Metal-Enclosed Switchgear is an advanced, high-performance power distribution solution designed for medium-voltage electricity control and protection. Engineered as a centre-mounted vacuum switchgear, it incorporates premium performance characteristics with a versatile drawout design. The system typically integrates the highly reliable ZN22B-12 vacuum circuit breaker as its main vacuum switch, and can also be seamlessly configured with ZN12-10, 3AF, or 3AH vacuum circuit breakers to meet varying project requirements.
Fully compliant with stringent industry standards including GB3906, DL404, and IEC298, the KYN18-12 is purpose-built for 3-10kV AC three-phase 50Hz single-busbar systems. It is widely deployed across modern power generation plants, substations, urban distribution networks, and heavy industrial/mining enterprises for efficient energy acceptance and distribution. Specially engineered for versatile grid layouts, the unit is optimized for non-against-the-wall installation, providing comprehensive rear-access serviceability.
-
Centre-Mounted Drawer Design: Removable / withdrawable breaker truck ensures effortless inspection, rapid maintenance, and minimum downtime during circuit breaker swapping.
-
Exceptional Interrupting Capability: Delivers heavy-duty short-circuit breaking current ratings up to 50kA, providing robust protection against severe system faults.
-
Robust Armoured Compartmentalization: Grounded metal partitions isolate the circuit breaker, main busbars, cables, and instrument panels into distinct, blast-resistant compartments to ensure premium operational safety.
-
Flexible Component Integration: Fully compatible with domestic and international vacuum circuit breakers (ZN22B-12, ZN12-10, 3AF, 3AH), allowing custom engineering according to client specifications.
K Y N 18 - 12 / □ - □ - □ - □
-
K: Metal-clad Armoured Type
-
Y: Removable / Withdrawable Type
-
N: Indoor Operation
-
18: Design Code / Sequence Number
-
12: Rated Voltage (kV)
-
□: Main Circuit Programme Number
-
□: Environmental Characteristics (TH for Humid heat belt; TA for Dry heat belt; Ordinary type without note)
-
□: Rated Current (A)
-
□: Rated Breaking Current (kA)
-
Ambient Air Temperature & Altitude Coordination: * Altitude ≤ 1000m: Ambient temperature up to +40°C.
-
Altitude ≤ 2000m: Ambient temperature up to +35°C (according to national standard correction).
-
Altitude ≤ 3000m: Ambient temperature up to +30°C.
-
-
Humidity & Environmental Protection: Daily average relative humidity ≤ 95%; Monthly average relative humidity ≤ 90%. For high-humidity environments, integrated heating and dehumidification equipment is utilized.
-
Seismicity / Earthquake Resistance: Safe for application in heavy-duty areas with seismic intensities up to 9 degrees.
-
Atmospheric Integrity: The surrounding atmosphere must remain completely free from corrosive gases, flammable or explosive gases, heavy water vapor, or dense particulate pollution.
-
Operation Limit: No regular strenuous physical exercise or heavy vibration in the installation area.
| Technical Parameter / Item | Unit | Value / Specification |
|---|---|---|
| Rated Voltage | kV | (3), 6, 10, 12 |
| Rated Short-Circuit Breaking Current | kA | 31.5 / 40 / 50 |
| Rated Current | A | 1250 / 1600 / 2000 / 2500 / 3150 |
| Rated Thermal Stability Current (Short-Time) | kA | 31.5 / 40 / 50 (Duration: 3s / 4s) |
| Rated Dynamic Stability Current (Peak) | kA | 80 / 100 / 125 |
| Rated Lightning Impulse Withstand Voltage | kV | 75 |
| Rated 1-min Power Frequency Withstand Voltage | kV | 42 |
| Shell and Compartment Protection Grade | - | IP30 |
-
High Seismic & Fault Resilience: Specially rated for extreme conditions, capable of withstanding seismic forces up to 9 degrees and absorbing short-circuit impacts up to 50kA, making it ideal for critical infrastructure.
-
Effortless Serviceability via Center-Mounted Drawer: The advanced removable handcart design permits swift maintenance, rapid testing, and minimal isolation delays, maximizing uptime for heavy industrial operations.
-
Uncompromising Multi-Compartment Armor: Rigid, grounded metal-clad isolation of high-voltage components ensures absolute personnel safety, successfully containing localized faults and preventing collateral damage.
-
Tailored for Severe Climates: Features highly flexible environmental adaptations (TH/TA options) coupled with smart automated anti-condensation heating systems to perform flawlessly across humid, tropical, and high-altitude regions.
-
Global Engineering Compliance: Meticulously compliant with IEC298 and GB3906 benchmarks, establishing it as a top-tier, low-maintenance power distribution asset trusted by utility grids and mining enterprises worldwide.
Get in Touch