Dual AC Line Voltage Monitor High Accuracy Line Power Monitor
Price:
RMB 1499
MOQ:
10 PCS
Delivery Time:
7-30 work days
Brand:
OEM / ODM
Product Description
Dual AC Line Power Monitor with High Accuracy Voltage Measurement and Industrial Grade Environmental Suitability
AC Monitor
Essential Monitoring Capabilities
Simultaneously monitors electrical parameters of two AC incoming lines and two AC busbars, including AC incoming line switch status, ATS system status, and feeder line location and tripping status signals.
Monitoring Functional Parameters
| Voltage/Current Measurement |
Voltage Accuracy: ±0.1%FS
Current Accuracy: ±0.5%FS
Resolution: Voltage: 0.1 V; Current: 0.01 A
|
|---|---|
| Frequency Monitoring |
Measuring Range: 40-70Hz
Accuracy: ±0.01Hz
|
| Power Quality Analysis (Selectable) |
Power Parameters: Active power (kW), reactive power (kvar), apparent power (KVA), power factor (PF)
Measuring Range: 0-1
Accuracy: ±0.5%
|
| Electricity Metering |
Cumulative bidirectional energy: Input/output (unit: kWh)
Accuracy: Class 0.5S (compliant with IEC 62053-22 standard)
|
| Harmonic Analysis | Total Harmonic Distortion (THD) monitoring (up to the 50th harmonic) |
| Voltage Fluctuation/Flicker | Complies with IEC 61000-4-30 standard |
Alarm Functions
- Overvoltage/Undervoltage Alarm
- Over-frequency/Under-frequency Alarm
- Busbar overload alarm
- Leakage Current Protection
All alarm thresholds are user-settable
Environmental Adaptability & Communication
| Communication Protocols | Modbus RTU, IEC 61850 (Power Automation), DNP3.0, CAN Bus |
|---|---|
| Interface Types | RS485, Ethernet, and fiber-optic communication (for interference-resistant applications) |
| Data Logging |
Historical Data Storage: Voltage, Current, and Power Curves (stored for ≥30 days)
Incident Record: Protection actions, fault waveforms (supports SOE event sequence recording)
|
Environmental Specifications
| Working Temperature | -25°C to +70°C (Industrial grade) |
|---|---|
| Humidity | 5%-95% RH, no condensation |
| Anti-vibration/Impact | Complies with IEC 60068-2-6 (Vibration) and IEC 60068-2-27 (Impact) |
| Electrical Isolation | Isolation voltage between input and output ≥ 2500 V AC |
| Electromagnetic Compatibility (EMC) | Complies with IEC 61000-4 (Electrostatic Discharge, Surges, Radio Frequency Interference) |
Certifications & Standards
| Security Certificates | CE, UL508 (Industrial Control Equipment), GB/T 14598 (Relay Protection) |
|---|---|
| Power Quality Standards | IEC 61000-4-30 (Class A), IEEE 519 (Harmonic Limiting) |
Software Functions
| Human-Machine Interface (HMI) |
Touchscreen display showing real-time data of the main circuit, alarm information, and electrical wiring diagram
Multi-language support (Chinese/English Interface)
|
|---|---|
| Remote Control | Supports remote control of incoming line switches and ATS |