General specifications | | |
Installation in hazardous area | Zone 2 / Div. 2 | SIL 2 |
Supply | | |
Connection | | Power Rail or terminals 11 (L+), 12 (L-) |
Rated voltage | Ur | 20 ... 30 V DC |
Ripple | | ≤ 10 % |
Rated current | Ir | 640 mA ... 365 mA |
Power dissipation | | max. 2.5 W |
Fieldbus connection
| | |
Number of segments | 1 | |
Rated voltage | UN | 12.6 ... 13.4 V |
PROFIBUS PA | | |
Connection | 3+, 6+, 2-, 5-, 1 shield, 4 shield | |
Rated voltage | 24... 26 V | |
Rated current | max. 400 mA | |
Terminating impedance | 100 Ω , integrated | |
PROFIBUS DP | PROFIBUS with RS-485 transmission technology | |
Connection | terminals 7 RxD/TxD-P, 8 RxD/TxD-N, 9 shield, 10 FE | |
Baud rate | 1.5 MBit/s max. | |
Indicators/operating means
| | |
Switch | PROFIBUS DP terminator | |
LED PWR | green: Power on | |
LED DP/ERR | red 2 Hz flashing: DP error red on: Hardware error red off: DP communication detected | |
LED PA | red 2 Hz flashing: No PA communication or overload Off: PA communication OK | |
Galvanic isolation | | |
PROFIBUS DP/PROFIBUS PA
| functional insulation acc. to IEC 62103, rated insulation voltage 50 V AC /70 V DC | |
PROFIBUS DP/Supply | basic insulation according to IEC/EN 61010, rated insulation voltage 253 V AC /357 V DC | |
PROFIBUS PA/Supply | basic insulation according to IEC/EN 61010, rated insulation voltage 253 V AC /357 V DC | |
Directive conformity | | |
Electromagnetic compatibility | | |
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | | |
Electromagnetic compatibility | NAMUR NE 21 | |
Degree of protection | IEC/EN 60529 | |
Fieldbus standard | EN 50170/2 | |
Climatic conditions | DIN IEC 721 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions
| | |
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | < 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g 10 ... 150 Hz | |
Pollution degree | max. 2, according to IEC 60664 | |
Corrosion resistance | acc. to ISA-S71.04-1985,severity level G3 | |
Mechanical specifications | | |
Connection type | screw terminal , pluggable | |
Core cross section | up to 2.5 mm2 | |
Housing material | Polycarbonate | |
Degree of protection | IP20 | |
Mass | 180 g | |
Mounting | DIN rail mounting | |
Data for application in connection with hazardous areas | | |
Certificate | TÜV 16 ATEX 7831 X | |
Marking | II 3G Ex ec IIC T4 Gc | |
Directive conformity | | |
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 | |
International approvals | | |
CSA approval | CSA 16.70064204 | |
Approved for | Class I, Division 2, Groups A, B, C, D Class I, Zone 2, Ex nA IIC T4 Gc | |
IECEx approval | IECEx TUR 16.0006X | |
Approved for | Ex ec IIC T4 Gc | |
General information | | |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. | |