Functional safety related parameters | | |
Safety Integrity Level (SIL) | SIL 3 | SIL 2 |
Supply | | |
Connection | via 14-channel flat cable from the KFD2-HMM-16 primary module | |
HART signal channels (non-intrinsically safe)
| | |
Conformity | HART field device input (revision 5 to 7) | |
Connection | 26-pin flat cable for analog connections 14-pin flat cable for primary module/secondary module connection between KFD2-HMM-16 and KFD0-HMS-16 | |
Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185°F) | |
Terminating resistor | external 230 ... 500 Ω standard (up to 1000 Ω possible) | |
Output voltage | ≥ 400 mV ss (with the terminator resistance specified above) | |
Output resistance | 100 Ω or smaller, capacitive coupling | |
Input impedance | according to HART specification | |
Input voltage range | 0.08 ... 4 V ss ; typ. ± 5.2 V as local reference | |
Indicators/settings | | |
Labeling | space for labeling at the front | |
Directive conformity
| | |
Electromagnetic compatibility | | |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions
| | |
Ambient temperature | -20 ... 65 °C (-4 ... 149 °F) | |
Mechanical specifications | | |
Degree of protection
| IP20 | |
Mass | approx. 100 g | |
Dimensions | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) (W x H x D) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | | |
Certificate | PF 07 CERT 1143 X | |
Marking | II 3G Ex nA IIC T4 Gc | |
Directive conformity | | |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
General information | | |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. | |