General specifications | | |
Signal type | Digital Input | Digital Input |
Functional safety related parameters | | |
Safety Integrity Level (SIL) | SIL 2 | SIL 2 |
Supply | | |
Connection | | Power Rail or terminals 14+, 15- |
Rated voltage | Ur | 20 ... 30 V DC |
Ripple | | ≤ 10 % |
Rated current | Ir | ≤ 50 mA |
Power dissipation | | 1 W |
Power consumption | | ≤ 1.3 W |
Input | | |
Connection side | | field side |
Connection | | terminals 1+, 2+, 3-; 4+, 5+, 6- |
Rated values | | acc. to EN 60947-5-6 (NAMUR) |
Open circuit voltage/short-circuit current | | approx. 8 V DC / approx. 8 mA |
Switching point/switching hysteresis | | 1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection | | breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
Pulse/Pause ratio | | min. 20 ms / min. 20 ms |
Output | | |
Connection side | | control side |
Connection | | output I: terminals 7, 8 ; output II: terminals 8, 9 ; output III: terminals 10, 11 ; output IV: terminals 11, 12 |
Output I, II, III, IV | | channel 1, 2; relay |
Contact loading | | 50 V AC/1 A/cos φ > 0.7; 40 V DC/1 A resistive load |
Minimum switch current | | 1 mA / 24 V DC |
Energized/De-energized delay | | approx. 20 ms / approx. 20 ms |
Mechanical life | | 108 switching cycles |
Collective error message | | Power Rail |
Transfer characteristics | | |
Switching frequency | ≤ 10 Hz | |