General specifications | | |
Signal type | Digital Input | Digital Input |
Functional safety related parameters | | |
Safety Integrity Level (SIL) | SIL 2 | SIL 2 |
Systematic capability (SC) | SC 3 | SC 3 |
Supply | | |
Connection | | Power Rail or terminals 14+, 15- |
Rated voltage | Ur | 19 ... 30 V DC |
Ripple | | ≤ 10 % |
Rated current | Ir | 20 ... 15 mA |
Power dissipation | | ≤ 1W including maximum power dissipation in the output |
Input | | |
Connection side | | field side |
Connection | | terminals 1+, 2+, 3- |
Rated values | | acc. to EN 60947-5-6 (NAMUR), see manual for electrical data |
Open circuit voltage/short-circuit current | | approx. 10 V DC / approx. 8 mA |
Switching point/switching hysteresis | | 1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection | | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA |
Pulse/Pause ratio | | min. 100 µs / min. 100 µs |
Output | | |
Connection side | | control side |
Connection | | output I: terminal 7,8 ; output II: terminal 8,9 |
Rated voltage | Ur | 30 V DC |
Rated current | Ir | 100 mA , short-circuit protected |
Response time | | ≤ 200 µs |
Signal level | | 1-signal: (external voltage) - 3 V max. for 100 mA 0-signal: blocked output (off-state current ≤ 10 µA) |
Output I | | signal ; Transistor |
Output II | | signal or fault message ; Transistor |
Collective error message | | Power Rail |
Transfer characteristics | | |
Switching frequency | ≤ 5 kHz | |