General specifications | | |
Signal type | Analog input | Digital Input |
Functional safety related parameters | | |
Safety Integrity Level (SIL) | | SIL 2 |
Systematic capability (SC) | | SC 3 |
Supply | | |
Connection | | Power Rail or terminals 9+, 10- |
Rated voltage | Ur | 19 ... 30 V DC |
Ripple | | within the supply tolerance |
Rated current | Ir | < 28 mA |
Power consumption | | 0.35 W (24 V and 1 mA sense current), 0.85 W (30 V and 10 mA sense current) |
Input | | |
Connection side | | field side |
Connection | | terminals 1, 2, 3, 4 |
Line fault detection | | yes , at Pt100 |
Lead resistance | | ≤ 10 % of resistance value |
Transmission range | | 0 ... 10 mA |
Available voltage | | 7 V |
Line fault detection | | < 30 nA |
Output | | |
Connection side | | control side |
Connection | | terminals 5-, 7-, 6+, 8+ |
Current | | 0 ... 10 mA |
Available voltage | | 0 ... 4.2 V |
Fault signal | | field voltage < 150 mV or > 4 V, depending on lead disconnected |
Reverse polarity protection | | for I < 10 mA or U < 20 V |
Transfer characteristics | | |
Accuracy | 0.1 % | |
Deviation | Im ≥ 1 mA: ±0.1 % of Rm or ± 0.1 Ω (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: ± 1 % of Rm or 1 Ω (the larger value is applicable). | |
Influence of ambient temperature | Im ≥ 1mA, Rm ≥ 100 Ω: 0.01 %/K in the range -20 ... +70 °C (-4 ... 158 °F) Im < 1 mA or Rm < 100 Ω: temperature stability reduces in proportion to Im or Rm | |
Settling time | ≤ 5 ms | |
Rise time/fall time | ≤ 2 ms (10 ... 90%) | |