Shenzhen HRD SCI&TECH CO.,Ltd
                                                                                                           
Verified Supplier
16 Years
Since 2010
Menu
Electrical Equipment & Supplies Batteries Uninterruptible Power Supply (UPS)

RT series Online HF UPS 1-3kva with output PF0.9 ,120Vac 60Hz

Price Negotiable
Price: 180- 380USD/PCS;
MOQ: 50PCS
Delivery Time: Within 4 weeks
Brand: HRD/ OEM/ ODM
Product Description

PC MAX Rackmount  Series Online HF UPS 1-3KVA, 110/120/127VAC
1:1 Phase Output PF: 1.0


 
 
 
 
 
 
 
 
 
 
 
 
 

 
Application:PC, workstation, network center, SOHO, server, industry equipment, medical equipment or other critical system.
Features:
Rack-Tower convertible
Two directions LCD display,gravity sensor
Online-Double conversion (PFC)
Full digital control (DSP)
Output power factor: 0.9
Economic Operation Mode (ECO)
Wide input voltage range
Self-testing when UPS startup

Emgergency Power Off(EPO)
Cold Start (DC)
Comprehensive protection for the total unit
Multifunctional LCD screen, setting output voltage, bypass etc…
Input neutral and live wires reverse detection
Optimized battery configuration: 1K-24V,2K-48/72V,3K-48/72/96V
Diverse options of accessories, intelligent management
Standard interface : USB ;SNMP /Dry contact Board optional
Specification
 
 

Model

RT01

RT02

RT03

Capacity

  Kva/Kw

1Kva/0.Kw

2Kva/2Kw

3Kva/3Kw

 

 

 

 

 

 

Input

 

 

Voltage

Low transfer

85Vac± 3% (Ph-N) @100% load , 65Vac± 3% (Ph-N) @50% load

Low back

95Vac(Ph-N) @ 100% load ; 75Vac (Ph-N) @50% load

High transfer

110/120/127Vac:155V± 3%

High back

110/120/127Vac:142Vac± 3%

Frequency range

50Hz/60Hz +/-4Hz(auto-detect)

phase

1:1phase ,L+N+G

Current THDI

<6%(100%nonlinear load)

Power Factor

≥0.99

Generate Input

Support

breaker

7A

16A

25A

ECO range

 108-132Vac

Bypass voltage range

 102-138Vac

Current harmonic

≦3%(100% non-linear load)

 

 

 

 

 

 

Output

 

 

Voltage

110/120/127(1-3Kva)

Power Factor

0.9 (0.8 optional)

Voltage regulation

± 2%

Frequency(Line Model)

50Hz/60Hz +/-4Hz

Frequency(Batt Model)

50/60Hz ± 0.02Hz

Current Crest Ratio

3:1

Harmonic Distortion

≤3% THD(Liner Load)

≤5% THD(Non-Liner Load)

Output waveform

Pure Sine wave

Outlet

Sockets(Optional)

Overload Capacity

105%<load<125% for 1 mins ,125%<load<150% for30sec

 

Efficiency

AC Mode

Full Load≥94%

Battery Mode

Full Load≥93%

ECO Mode

Full Load≥97%

 

 

 

 

 

Battery

Number of Battery

2/3

4/6

6/8

Battery Type

Sealed, lead-acid, maintenance-free

standard model: 12V/7AH OR 9AH inbuilt

long run model: battery external, capacity optional

Back Time

Standard unit: 5-12mins;

Long-run unit:

depends on external battery

Standard unit: 8-18mins;

Long-run unit:

depends on external battery

Standard unit:5-12mins;

Long-run unit:

depends on external battery

Recharge Time(to 90%)

5 Hours

5 Hours

5 Hours

Charge Current(standard unit)

1.0A

1.0A

1.0A

Charge Current(long run unit)

7.0A

7.0A

7.0A

 

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Shenzhen HRD SCI&TECH CO.,Ltd
Location 1st floor, 56A building, Bao’tian Industrial Park,Xixiang Town Bao’an District, Shenzhen City
Contact Person Hunter Chen

Request A Quote

Please check your email address.
Your message must be at least 20 characters.