Current Transformer Test Set IEC60044-1 CT Analyzer KT210

 

Description Of Current Transformer Analyzer

Complete measurement function, it can test all type current transformer for secondary overload, secondary loop resistance, excitation characteristic, transient characteristic, ratio difference, angle difference and polarity. It can also test exact limit coefficient(ALF), device security coefficient(FS), secondary time constant(Ts), remanence coefficient(Kr), transient area coefficient(Ktd), inflexion voltage, current, level, saturation inductance, un-saturation inductance, 5% 10% error curve, of current transformer, hysteresis loop for current transformer, and evaluate test result according to defined standard.

 

Feature Of Current Transformer Test Set

High measurement accuracy, resistance accuracy is 0.1%+1mΩ, phase accuracy±0.05 degree, variable accuracy is ±0.1% (1-5000 ), variable accuracy is ±0.2%(5000-10000).
It can test current transformer according to IEC60044-1, IEC60044-6, IEC61869-2 and ANSI30/45 standard etc.
Complete measurement function, it can test all type current transformer for secondary overload, secondary loop resistance, excitation characteristic, transient characteristic, ratio difference, angle difference and polarity. It can also test exact limit coefficient(ALF), device security coefficient(FS), secondary time constant(Ts), remanence coefficient(Kr), transient area coefficient(Ktd), inflexion voltage, current, level, saturation inductance, un-saturation inductance, 5% 10% error curve, of current transformer, hysteresis loop for current transformer, and evaluate test result according to defined standard.
PT Test As for those inductive PT based on the definition of GB1207-2006(IEC60044-2), KT210 CT/PT Analyzer can also test them. KT210 CT/PT Analyzer can do variable ratio, polarity and secondary winding excitation test of inductive PT.

 

Specification Of Current Transformer Test Device

Voltage Measurement Input
Secondary Input Range 0~300V
Max Knee point 30KV
Secondary Input Accuracy ±0.1%
Primary Input Range 0~30V
Primary Input Accuracy ±0.1%
 
Output
Output Voltage 0 Vac to 120 Vac
Output Current 0 A to 5 A (15 A peak)
Output Power 0 VA to 450 VA (1500 VA peak)
 
Main Power Supply
Input Voltage 176 Vac to 264 Vac @ 10A Max
Permissible Input Voltage 120 Vdc to 370 Vdc @ 5A Max
Frequency 50 / 60 Hz
Permissible Frequency 47 Hz to 63 Hz
Connection Standard AC socket 60320
 
Physical Dimensions
Size (W x H x D) 360 x 140 x 325mm
Weight <8 kg (without accessories)
 
Environment Conditions
Operating Temperature -10°C up to + 55°C
Storage Temperature -25°C up to + 70°C
Humidity Relative humidity 5% up to 95% not condensing

 

Advantage Of Current Transformer Test System

Easy to operate CT / PT Analyzer,
120V / 15A Current Output,
9.7 inch touch screen operation,
IEC60044-1, IEC60044-6, IEC61869-2, ANSI30/45 standard
High stability for bushing CT testing;

 

FAQ

Q: Can the device test the function of Synchronising or synchronism-check relays?

A: Yes.

Q: How about the guarantee of repair?

A: All of our products have 3-years guarantee of free repair, and life-long maintenance.

Q: What is your technical advantages?

A: Easy to operate, measure quickly, all test can be done automatically based on the same connection line type except overload impedance measurement.

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Kingsine Electric Automation Co., Ltd.
Location 6/F, Block 4-CD, TianAn Cyber Park, Futian District, Shenzhen 518048,.China
Contact Person Amy

Request A Quote

Please check your email address.
Your message must be at least 20 characters.