Electronic Cummins Diesel Generators With Water Cooling, 500kva, 3 phase,50HZ,open type
1, Model:CCEC Cummins KTA19-G3
2, Air Intake System:Turbo, Water/Air cooling
3, Fuel System:PT type fuel pump, EF
4, Cylinder Arrangement:6 in line
6, Bore and Stroke:159*159(mm)
7, Rated RPM:1500rpm
8, Max. Standby Power at Rated RPM:1227KW/1669HP
9, Governor Type:Electronic
400KW / 500KVA Cummins Diesel Generator Sets , KTA19-G3
|
Standby Power(50Hz) |
400KW / 500KVA |
|
Prime Power(50Hz) |
360KW / 450KVA |
Dimension & Weight
|
Standard Configuration (Open Type) |
|
Overall Size: 3400(mm)×1380(mm)×1980(mm) |
|
Weight: 4000kg |
|
General Features: |
|
Engine (CCEC Cummins KTA19-G3) |
|
Radiator 40OC max, fans are driven by belt, with safety guard |
|
24V charge alternator |
|
Alternator: single bearing alternator IP23, insulation class H/H |
|
Absorber |
|
Dry type air filter, double fuel filter, oil filter, coolant filter |
|
Main line circuit breaker |
|
Standard control panel |
|
Two12V batteries, rack and cable |
|
Ripple flex exhaust pipe, exhaust siphon, flange, muffler |
|
User manual |
Engine Data
|
Manufacturer / Model |
CCEC Cummins KTA19-G3, 4-cycle |
|
Air Intake System |
Turbo, Water/Air cooling |
|
Fuel System |
PT type fuel pump, EF |
|
Cylinder Arrangement |
6 in line |
|
Displacement |
18.9 |
|
Bore and Stroke |
159*159(mm) |
|
Compression Rate |
14.5 |
|
Rated RPM |
1500rp |
|
Max. Standby Power at Rated RPM |
448KW/609H |
|
Governor Type: |
Electronic |
|
Exhaust System |
|
|
Exhaust Gas Flow |
1489L/s |
|
Exhaust Temperature |
532℃ |
|
Max Back Pressure |
10kPa |
|
Air Intake System |
|
|
Max Intake Restriction |
6.23kPa |
|
Consumption |
533L/s |
|
Intake Flow |
9800 L/s |
|
Fuel System |
|
|
100%( Prime Power) Loa |
204.6 g/Kw.h |
|
75%(Prime Power) Loa |
205.4 g/Kw.h |
|
50%(Prime Power) Load |
215.7 g/Kw.h |
|
100%( Prime Power) Loa |
92.4L/h |
|
Oil System |
|
|
Total Oil Capacity |
50L |
|
Oil Consumption |
≤4g/kw |
|
Engine Oil Tank Capacity |
38L |
|
Oil Pressure at Rated RPM |
345-483kPa |
|
Cooling System |
|
|
Total Coolant Capacity |
91L |
|
Thermostat: |
82-93℃ |
|
Max Water Temperature |
104℃ |
Alternator SpecifiCAT-parts-partsion
GENERAL DATA
Compliance with GB755, BS5000, VDE0530, NEMAMG1-22, IED34-1, CSA22.2 and AS1359 standards.
Alternator Data
|
Number of Phase: |
3 |
|
Connecting Type: |
3 Phase and 4 Wires, “Y” type connecting |
|
Number of Bearing: |
1 |
|
Power Factor: |
0.8 |
|
Protection Grade: |
IP23 |
|
Altitude: |
≤1000m |
|
Exciter Type: |
Brushless, self-exciting |
|
Insulation Class, Temperature Rise: |
H/H |
|
Telephone Influence Factor (TIF): |
<50 |
|
THF: |
<2% |
|
Voltage Regulation, Steady State: |
≤±1% |
|
Alternator Capacity: |
500KVA |
|
Alternator Efficiencies: |
93.8% |
|
Air Cooling Flow: |
1.035m3/s |
|
|
|
Generating set data:
|
Voltage Regulation: |
≥±5% |
|
Voltage Regulation, Stead State: |
≤±1% |
|
Sudden Voltage Warp (100% Sudden Reduce): |
≤+25% |
|
Sudden Voltage Warp (Sudden Increase): |
≤-20% |
|
Voltage Stable Time (100% Sudden Reduce): |
≤6S |
|
Voltage Stable Time (Sudden Increase) |
≤6S |
|
Frequency Regulation, Stead State: |
≤5% |
|
Frequency Waving: |
≤0.5% |
|
Sudden Frequency Warp (100% Sudden Reduce): |
≤+12% |
|
Sudden Frequency Warp (Sudden Increase): |
≤-10% |
|
Frequency Recovery Time (100% Sudden Reduce): |
≤5S |
|
Frequency Recovery Time (Sudden Increase): |
≤5S |
Competitive Advantage:
High Performance of loading Easy start
Nice protection User-friendly operation
Low running cost Environmental Long service life
SpecifiCAT-parts-partsion
Get in Touch