■ ZION COMMUNICATION — FR6387-UN-0225
Fire Resistant Cable 2 × 2.5 sq mm | BS 6387 / IEC 60331 / LSZH (Red RAL 3000)
General Information
| Item |
Specification |
| Product Name |
Fire Resistant Cable |
| Model No. |
FR6387-UN-0225 |
| Construction Type |
CU / FR / LSZH (Unscreened) |
| Conductor Material |
Stranded Bare Copper (Class 5, EN 60228) |
| Conductor Size |
45 × 0.25 mm |
| Nominal Cross Section |
2 × 2.5 sq mm |
| Rated Voltage |
600 / 1000 V |
| Operating Temperature |
−30 °C ~ +90 °C |
| Outer Color |
Red RAL 3000 |
| Applicable Standards |
IEC 60331-21 (FE180), BS 6387 CAT B/C, IEC 60332-1-2, IEC 60332-3-24, EN 50200 PH120, CE, RoHS |
Construction Details
| Component |
Material / Description |
Standard |
Dimensions |
| Conductor |
Stranded Bare Copper |
EN 60228 |
45 × 0.25 mm |
| DC Resistance (20 °C) |
— |
EN 60228 |
7.98 Ω/km |
| Insulation |
Silicone Rubber (Heat-Resistant) |
IEC/EN 60811-203 |
0.58 mm thick |
| Insulation Diameter |
— |
IEC/EN 60811-201 |
3.1 ± 0.1 mm |
| Insulation Colors |
Brown / White |
— |
— |
| Insulation Resistance |
> 200 MΩ/km |
— |
— |
| Fire Barrier Layer |
Mica Tape |
— |
0.14 × 24 mm |
| Overall Screen |
— (Unscreened Type) |
— |
— |
| Drain Wire |
— |
— |
— |
| Outer Sheath |
LSZH (Low Smoke Zero Halogen) |
IEC/EN 60811-202 |
0.7 mm thick |
| Outer Diameter |
— |
IEC/EN 60811-203 |
7.8 ± 0.2 mm |
| Pitch of Twist |
— |
— |
176 ± 10 mm |
| Inductance |
— |
— |
2.3 mH/km |
| High-Voltage Test |
EN 50288-7 |
3.0 kV / 1 min |
— |
■ Fire & Safety Performance
| Test Item |
Standard |
Description / Requirement |
| Fire Resistance |
IEC 60331-21 (FE180) / BS 6387 CAT B, CAT C |
Maintains circuit integrity for 180 min at 750–950 °C |
| Flame Propagation |
IEC 60332-1-2 / IEC 60332-3-24 / EN 50266-2-4 |
Restricts flame spread on single and bunched cables |
| Smoke Density |
IEC 61034-1/2 |
Low smoke emission for visibility and safety |
| Corrosive Gas Emission |
IEC 60754-1/2 / EN 50267 |
Low acid gas release, halogen-free |
| RoHS Compliance |
EU Directive 2011/65/EU |
Confirmed (Pb, Cd, Hg, Cr⁶⁺, PBB, PBDE Free) |
■ Electrical & Mechanical Characteristics
-
Insulation Resistance: > 200 MΩ/km
-
Voltage Withstand: 3.0 kV (1 min)
-
Inductance: 2.3 mH/km
-
Operating Temperature: −30 °C ~ +90 °C
-
Minimum Bending Radius: 10 × Cable OD
-
Fire Survival Duration: 180 min (FE180 / PH120)
■ Applications
-
For fire-alarm, emergency lighting, and control circuits requiring continuous operation during fire
-
Life-safety and evacuation systems
-
Fire-pump and sprinkler controls
-
Tunnel, airport, hospital, and industrial infrastructure
■ Key Features
-
FE180 / PH120 Protection: Circuit integrity for 180 min at 950 °C
-
LSZH Outer Sheath: Minimal smoke and zero halogen gas emission
-
Silicone + Mica Insulation: Superior heat and electrical stability
-
✅ Certified Safety: Conforms to IEC, BS, EN, CE & RoHS requirements