| CU/XLPE/PVC/AWA/PVC 0.6/1KV Cable |
|
![]()
![]()
|
| Application: |
Cable Standards: |
General single core PVC cable with aluminium wire armour(AWA)
control / power cable for fixed wiring arrangements and power networks.
Suitable for underground, indoor and outdoor use in cable ducting. |
Flame propagation to BS EN 60332-1-2 |
| BS5467 |
| IEC/EN 60228 |
| |
| Product Description: |
| Conductor |
Stranded Plain Annealed Circular Copper Conductor |
| Insulation |
Cross Linked Polyethylene (XLPE) |
| Bedding |
PVC |
| Armour |
Aluminium Wire |
| Sheath |
PVC |
| |
| Characteristics: |
| Voltage Rating |
600/1000 Volts |
| Temperature Limits |
-15°C to +90°C |
| |
| Core Identification: |
| Brown Inner |
|
|
|
|
Should not be installed at temperatures below 0°C or above +60°C
![]()
|
| Dimensions: |
| Zion Code |
Conductor Size (mm2) |
Stranding (mm) |
No. Of
Cores |
Weight Kg/km |
Overall
Diameter
(mm) |
Brass
A2 |
Nylon
A2 |
Nylon
Cleat |
Trefoil
Cleat |
| 71501-50 |
50 |
19/1.78 |
1 |
638 |
17.70 |
20 |
25 |
0.7 |
- |
| 71501-70 |
70 |
19/2.14 |
1 |
891 |
19.60 |
25 |
32 |
0.8 |
- |
| 71501-95 |
95 |
19/2.52 |
1 |
1166 |
21.50 |
25 |
32 |
0.9 |
- |
| 71501-120 |
120 |
37/2.03 |
1 |
1412 |
23.10 |
25 |
32 |
1.0 |
- |
| 71501-150 |
150 |
37/2.25 |
1 |
1800 |
26.00 |
32 |
40 |
1.1 |
- |
| 71501-185 |
185 |
37/2.52 |
1 |
2200 |
28.00 |
32 |
40 |
1.2 |
TASB04 |
| 71501-240 |
240 |
61/2.25 |
1 |
2800 |
32.00 |
40 |
50S |
1.4 |
TASB06 |
| 71501-300 |
300 |
61/2.52 |
1 |
3400 |
33.00 |
40 |
50S |
1.4 |
TASB06 |
| 71501-400 |
400 |
61/2.85 |
1 |
4450 |
38.00 |
40 |
50 |
1.6 |
TASB10 |
| 71501-500 |
500 |
61/3.2 |
1 |
5550 |
43.00 |
50S |
63S |
1.8 |
TASB13 |
| 71501-630 |
630 |
127/2.52 |
1 |
7100 |
47.00 |
50 |
63S |
2.0 |
TASB15 |
| |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Current Carrying Capacity: |
| THE ABOVE IS IN ACCORDANCE WITH 18TH EDITION OF IET WIRING REGULATIONS |
| CONDUCTOR CROSS – SECTIONAL AREA |
REFERENCE METHOD C (CLIPPED DIRECT) |
REFERENCE METHOD F (IN FREE AIR ON A PERFORATED CABLE TRAY HORIZONTAL / VERTICAL) |
| TOUCHING |
TOUCHING |
SPACED BY ONE DIAMETER |
| 2 CABLES, SINGLE - PHASE AC OR DC FLAT |
3 OR 4
CABLES, 3 PHASE AC FLAT |
2 CABLES, SINGLE - PHASE AC OR DC FLAT |
3 CABLES,
3 PHASE AC FLAT |
3 CABLES, THREE - PHASE AC TREFOIL |
2 CABLES DC |
2 CABLES, SINGLE PHASE AC |
3 OR 4 CABLES,
THREE-PHASE AC FLAT |
| HORIZONTAL |
VERTICAL |
HORIZONTAL |
VERTICAL |
HORIZONTAL |
VERTICAL |
| 1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
| (MM²) |
(A) |
(A) |
(A) |
(A) |
(A) |
(A) |
(A) |
(A) |
(A) |
(A) |
(A) |
| 50 |
237 |
220 |
253 |
232 |
222 |
284 |
270 |
282 |
266 |
288 |
266 |
| 70 |
303 |
277 |
322 |
293 |
285 |
356 |
349 |
357 |
337 |
358 |
331 |
| 95 |
367 |
333 |
389 |
352 |
346 |
446 |
426 |
436 |
412 |
425 |
393 |
| 120 |
425 |
383 |
449 |
405 |
402 |
519 |
497 |
504 |
477 |
485 |
449 |
| 150 |
488 |
437 |
516 |
462 |
463 |
600 |
575 |
566 |
539 |
549 |
510 |
| 185 |
557 |
496 |
587 |
524 |
529 |
688 |
660 |
643 |
614 |
618 |
574 |
| 240 |
656 |
579 |
689 |
612 |
625 |
815 |
782 |
749 |
714 |
715 |
666 |
| 300 |
755 |
662 |
792 |
700 |
720 |
943 |
906 |
842 |
805 |
810 |
755 |
| 400 |
853 |
717 |
899 |
767 |
815 |
1137 |
1094 |
929 |
889 |
848 |
797 |
| 500 |
962 |
791 |
1016 |
851 |
918 |
1314 |
1266 |
1032 |
989 |
923 |
871 |
| 630 |
1082 |
861 |
1146 |
935 |
1027 |
1528 |
1474 |
1139 |
1092 |
992 |
940 |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Voltage Drop |
CONDUCTOR CROSS – SECTIONAL AREA
MM2 |
2 CABLES DC |
REFERENCE METHODS C AND F (CLIPPED DIRECT, ON TRAY OR IN FREE AIR) |
| 2 CABLES SINGLE PASS AC |
3 OR 4 CABLES THREE PHASE AC |
| TOUCHING |
SPACED |
TREFOIL / TOUCHING |
FLAT / TOUCHING |
FLAT / SPACED |
| |
|
R |
X |
Z |
R |
X |
Z |
R |
X |
Z |
R |
X |
Z |
R |
X |
Z |
| 50 |
0.980 |
0.990 |
0. 210 |
1.000 |
0.980 |
0.290 |
1.000 |
0.86 |
0.180 |
0. 870 |
0.840 |
0.250 |
0.880 |
0.840 |
0.330 |
0.90 |
| 70 |
0.670 |
0.680 |
0.200 |
0.710 |
0.690 |
0.290 |
0.750 |
0.59 |
0.170 |
0.620 |
0.600 |
0.250 |
0.650 |
0.620 |
0.320 |
0.70 |
| 95 |
0.490 |
0. 510 |
0.195 |
0.550 |
0.530 |
0.280 |
0.600 |
0.44 |
0.170 |
0. 470 |
0.460 |
0.240 |
0. 52 |
0.490 |
0. 310 |
0.58 |
| 120 |
0.390 |
0. 410 |
0.190 |
0.450 |
0.430 |
0.270 |
0. 51 |
0.35 |
0.165 |
0.390 |
0.380 |
0.240 |
0.440 |
0. 410 |
0.300 |
0. 51 |
| 150 |
0. 310 |
0.330 |
0.185 |
0.380 |
0.360 |
0.270 |
0.450 |
0.29 |
0.160 |
0.330 |
0. 310 |
0.230 |
0.390 |
0.340 |
0.290 |
0.45 |
| 185 |
0.250 |
0. 270 |
0.185 |
0.330 |
0.300 |
0.260 |
0.400 |
0.23 |
0.160 |
0.280 |
0.260 |
0.230 |
0.340 |
0.290 |
0.290 |
0. 41 |
| 240 |
0.195 |
0. 210 |
0.180 |
0.280 |
0.240 |
0.260 |
0.350 |
0.18 |
0.155 |
0.240 |
0. 210 |
0.220 |
0.300 |
0.240 |
0.280 |
0.37 |
| 300 |
0.155 |
0.170 |
0.175 |
0.250 |
0.195 |
0.250 |
0.320 |
0.145 |
0.150 |
0. 210 |
0.170 |
0.220 |
0.280 |
0.200 |
0. 270 |
0.34 |
| 400 |
0. 115 |
0.145 |
0.170 |
0.220 |
0.180 |
0. 24 |
0.300 |
0.125 |
0.150 |
0.195 |
0.160 |
0. 210 |
0.270 |
0.200 |
0. 270 |
0.33 |
| 500 |
0.093 |
0.125 |
0.170 |
0.210 |
0.165 |
0. 24 |
0.290 |
0.105 |
0.145 |
0.180 |
0.145 |
0.200 |
0.250 |
0.190 |
0.240 |
0. 31 |
| 630 |
0.073 |
0.105 |
0.165 |
0.195 |
0.150 |
0.230 |
0.270 |
0.092 |
0.145 |
0.170 |
0.135 |
0.195 |
0. 24 |
0.175 |
0.230 |
0.29 |
| |
The Above Is In Accordance With 18th Edition Of Iet Wiring Regulations
Conductor Operating Temperature: 90°c
R = Resistive Component
X = Reactive Component Z = Impedance Value
Spacing’s Larger Than Those Specified Will Result In Larger Volt Drop.
The Above Is In Accordance With 17th Edition Of Iee Wiring Regulations. |