1. Specifications
(1) Technical Parameters
| Item | Type | Technical Parameter |
| Structure | Dimension |
External Size H×W×D 1500×700×700mm
|
| Layout | 1 compartment | |
| Equipment Installation Method | 19” rack | |
| Door | With one front door, and special lock for outdoor cabinet (support padlock) | |
| Material | 1.5mm Galvanized steel | |
| Heat Insulation | 20mm PEF | |
| Structure | Assembled | |
| Ingress Protection | IP55 | |
| Temperature Control | Cooling | AC220V air conditioner and DC48V fans |
| Lighting | LED lamp | 48V LED lamps (immovable), with protective circuit breaker |
| Temperature | Temperature | Working Temperature: -40°C ~ +55°C |
| Storage Temperature: -50°C ~ + 70°C | ||
| Transport Temperature: -50°C ~ +70°C | ||
| Humidity | Relative Humidity | 5% ~ 100% |
| Pressure | Air Pressure | 62kpa ~ 101kpa (similar to 0m ~ 5000m altitude) |
| Radiation Intensity | Solar Radiation Intensity | 1120 ×(1±5%)W/m2 |
(2)Accessories List
| No. | Item | Quantity | Unit | Specs |
| 1 | Outdoor Telecom Cabinet | 1 | Set |
(1) External Size H×W×D 1500×700×700mm (2) One compartment: equipment compartment (3)With one front door, and special lock for outdoor cabinet (support padlock) (4) Material: 1.5mm galvanized steel,single wall (5)Heat insulation material 20mm PEF. |
| 2 | Air Conditioner | 1 | Set |
Power supply: AC220V, 50HZ, Cooling capacity: 1000W |
| 3 | Auxiliary Direct Ventilation Fans | 2 | PC | 12038 DC48V |
| 4 | Environment Monitoring Unit(Optional) | 1 | Set |
19 inch installation, 1U high, 48VDC input voltage, communication port: SNMP 9-way passive switching value input, 6-way active switching value input, 6-way relay output. |
| 5 | Water Sensor | 1 | PC | |
| 6 | Smoke Sensor | 1 | PC | |
| 7 | Temperature&Humidity sensor | 1 | PC | |
| 8 | Door Sensor | 2 | PC | One for controlling LED lamp, the other for open door alarm |
| 9 | LED Lamp | 1 | PC | DC48V |
| 10 | Package | 1 | Set | Wooden Case |
2. Applications
The ET7070150-EQ Outdoor Telecom Equipment Cabinet is mainly used in wireless communication base station, such as communication/network integrated service, 4G system, access/transmission switching station, emergency communication/transmission, etc.
3. Cabinet Picture
4. Features
4.1 The cabinet is dustproof, sunproof and rainproof, which is used in outdoor environment.
4.2 The cabinet cooling uses air conditioner and fans.
4.3 Including -48VDC illumination lamp.
4.4 The layout of the cabinet is reasonable, which will facilitate cable access, fixing and grounding. At the bottom of the cabinet, there are entrance holes individually for power cable, signal cable and optical cable.
4.5 All the cables, sealing and heat insulation used in the cabinet are made from flame retardant materials.
4.6 The cabinet includes 19” standard installation rack.
4.7 Material: good quality galvanized steel
4.8 Surface treatment: degreasing, derusting, rustproof phosphating (or galvanizing), powder coated.
4.9 Cabinet load bearing: ≥600kg
4.10 Ingress protection: IP55
4.11 Flame retardance: comply with GB5169.7 test A
4.12 Mechanical strength: each surface can bear upright pressure >980N; after the door is open, its outer end can bear upright pressure >200N.
4.13 Insulation resistance: the insulation resistance between grounding devices and cabinet body parts is not lower than 2×104M/500V(DC).
4.14 Withstand voltage: the withstand voltage between grounding devices and cabinet body parts is not lower than 3000V(DC)/1min.
5. Components Installation
LED lamp, smoke sensor and door sensor are installed at the top of the cabinet.
Air Conditioner and fans are installed on the door of the cabinet.
6. Cable Inlet
Feeder cable and other external cables all use bottom wiring method.
7. Grounding Protection
- The cabinet includes grounding copper bar with anti-corrosion coating. There are enough screws for wiring connection terminals.
- The metal part of the cabinet should be interconnected and be connected with grounding bar. Connection resistance between any two points is lower than 0.1Ω.
- Protective earthing of other equipments inside the cabinet should be connected to the grounding bar.
8. Theft Proof Design
8.1 Door lock theft proof design
- Damage resistance of the theft proof lock meets GA/T 73-1994 “Mechanical Anti-theft Lock” class B requirement, supporting padlock
- Three point lock
8.2 Connection and Fastening
(1) Use anti-loose threaded connection as structure and bearer connection. Anchor bolt for fixing cabinet use hot dip galvanized bolts.
(2) Door hinges use inner hinge mode.
8.3 Appearance and Surface Treatment
Cabinet surface coating is outdoor special powder coating, with white gray color (PANTONE 428C). The coating complies with GB/T 3181-2008 requirement.
8.4 Quality Control Introduction
Our company resolutely implements the principle of quality first, we control and supervise the whole production process in strict accordance with the requirements of the ISO9001 system and the related implementation process. The quality department strictly controls all aspects like material inspection, production processes, product testing, shipment inspection and establishes traceable documents and product identification.
Our quality inspection team, is very familiar with the various standards, strict implementation of the standards required sampling and testing methods.
9. Packing and Shipping
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.