5U Industrial Intelligent Telecom Rectifier Solution AC to DC48V with Remote Management
5U Industrial Intelligent Telecom Rectifier Solution AC to DC48V with Remote Management
Product Overview of 5U 18kW Intelligent Telecom Rectifier
The 18kW DC48V rectifier system delivers robust and uninterrupted DC power tailored for telecommunications, data centers, and industrial operations where system availability is non-negotiable. Operating from a 380VAC three-phase input, it supplies a stable and adjustable DC output ranging from –43 VDC to –58 VDC, nominally set at –53.5 VDC. Its advanced power conversion technology achieves better than 96% efficiency across the load range, making it an optimal fit for energy-sensitive and space-constrained installations.
AC Input Section of 5U 18kW Intelligent Telecom Rectifier
-
Voltage: 380VAC three-phase
-
MCB: 1 x 63A 3P+N circuit breaker
-
Frequency: 45Hz to 65Hz (rated 50Hz/60Hz)
-
SPD: Grade C, 20kA/40kA, 8/20μs
DC Distribution Section of 5U 18kW Intelligent Telecom Rectifier
-
Output voltage: -43 to -58VDC (rated -53.5VDC)
-
Maximum capacity: 18kW (6 x 3kW modules, N+1 redundancy)
-
Battery breaker: 2 x 125A/1P
-
LLVD: 3 x 63A/1P + 2 x 40A/1P + 2 x 32A/1P
-
BLVD: 2 x 16A/1P + 2 x 10A/1P + 2 x 6A/1P
Application Scenarios of 5U 18kW Intelligent Telecom Rectifier
-
Large 5G macro base stations
-
Telecom central offices and exchanges
-
Industrial manufacturing facilities
-
Data center backup power systems
-
Utility substation communication huts
-
Hospital telecom and IT rooms
-
Airport communication infrastructure
-
Railway signaling power systems
Specification of 5U 18kW Intelligent Telecom Rectifier
| Type | 18KW DC48V Rectifier System | |||
| General | Size | 482mm*350mm*5U(Width*Depth*Height) | ||
| Weight | ≤21kg (rectifiers excluded) | |||
| Cooling method | Natural cooling | |||
| Installation | 19-inch standard rack-mounted | |||
| Cabling mode | In and out from the top | |||
| Maintenance mode | From front side, support module grade change | |||
| Protection grade | IP20 | |||
| AC Input |
Voltage |
380VAC three-phase | ||
| MCB | 1 x 63A 3P+N circuit breaker | |||
| Frequency | 45Hz to 65Hz, rated value: 50Hz/60Hz | |||
| SPD | Grade C, 20KA/40KA, 8/20μs | |||
| DC Distribution |
Output voltage | -43~-58VDC, rated value: -53.5VDC | ||
|
Output capacity (Maximun)
|
18kw(6 x 3kw, supports N+1 redundancy) | |||
|
Battery breaker
|
2 x 125A 1P | |||
| LLVD | 3*63A/1P+2*40A/1P+2*32A/1P | |||
| BLVD |
2*16A/1P+2*10A/1P+2*6A/1P |
|||
| Rectifier Module | Input voltage | 85VAC to 300VAC, rated 220VAC | ||
| Efficiency | >96% | |||
| Rated power | 3000W(176 to 300VAC) | |||
| Working temperature | -40℃~+75℃(full performance below 50℃) | |||
| Dimension | 106.5mm(W)×286mm(D)×41.5mm(1U height) | |||
| Weight | ≤2kg | |||
| Cooling mode | Forced cooling | |||
| Power factor | ≥0.99 | |||
| THD | ≤5% | |||
| DC output | –43 ~ –58VDC, rated –53.5VDC, maximum 55A | |||
| Controller | Model | MC2900 | ||
| Signal input port | 3 AI(2 battery temp, 1 environment) , 7 DI | |||
| Alarm output port | 6 dry contact | |||
| Communication port | 1*RS485, 1*LAN | |||
| Situation Display | LCD | |||
| Environment | Operating temperature |
-40℃ ~ +65℃ (full output below 50℃) | ||
| Storage temperature | -40℃~+70℃ | |||
| Operating humidity | 5%~95%(non-condensing) | |||
| Altitude | 0~3000m(If the altitude is within the range of 2000m to 3000m, the maximum operating temperature decreases by 1℃ as the altitude increases by 200m.) |
|||