Outdoor Cabinet Air Conditioner Low Energy Consumption 60HZ AC220V 1500W
Outdoor Cabinet Air Conditioner Low Energy Consumption 60HZ AC220V 1500W
Quick Details:
| Place of Origin: Shenzhen, China (Mainland) | Rated Cooling Capacity : 1500W |
| Brand Name: ESTEL | Rated Heating Capacity:300/500W (optional) |
| Model: TC06-150JFH/01(KT041 AC220V 60Hz) | Dimension: H×W×D 695×424×220mm |
| Product Name: Outdoor Enclosure Air Conditioner | Input Voltage: AC220V/60Hz |
| Certification: ISO9001, CE, 3C, FCC, TLC | Rated Input Current:3.2A |
| Cover Material: galvanized steel | Rated Input Power: 704W |
| Color: Grey | Working Temperature: -20°C ~ +55°C |
| Protection Level: IP55 | Noise: ≤65dB |
| Installation Mode: door mounted, side mounted | Refrigerant: R410A |
| Support OEM | Cooling Method: compressor, active cooling |
Payment & Shipping Terms:
| Minimum Order Quantity: | 1 set |
| Price: | negotiation |
| Payment Terms: | L/C, D/A, D/P, T/T, Western Union |
| Supply Ability: | 1,4000 sets per month |
| Delivery Time: | 7-10 working days |
| Packaging Details: | carton + wooden case |
1. Specifications
Technical Parameters
| Environmental Performance | working environmental temperature | -20°C ~ 55°C |
| storage temperature | -40°C ~ 70°C | |
| working humidity | ≤95% | |
| Thermal Performance | rated cooling capacity | 1500W |
| rated heating capacity | 300W/500W (optional) | |
|
Electrical Performance |
rated input current | 3.2A |
| rated input power | 704W | |
| input voltage |
AC220V (185V~264V) |
|
| Noise | ≤65dB | |
| Reliability | MTBF | 70000h |
| Refrigerant | R410A | |
Dimension Diagram: H×W×D: 695×424×220mm
2. Description
TC06-150JFH/01(KT041 AC220V 60Hz) cabinet air conditioner is actively cooling with compressor, and it will remove the heat inside the cabinet to outside. It also can keep the dust and heat outside the cabinet, avoiding problems from using fan. The inside cabinet can be maintained at an ideal temperature for electrical components which effectively guarantees the stability of the electronic equipment and improves the reliability of the whole system.
3. Application
The cabinet air conditioner is widely applied in outdoor telecom cabinet, outdoor battery cabinet, electric cabinet, industry control cabinet, outdoor base station cabinet, etc.
4. Features
Strong adaptability
High intelligence
High precision
High reliability
Low noise
Low energy consumption
Easy installation, easy maintenance
With 4 way switching value detection
With 1 way room air conditioner control
Voltage input range: 220VAC±15% 60Hz
With dry contact alarm output
5. System Principle Diagram
6. Electrical Wiring Diagram
Wiring Ports:
L N PE : power supply port (voltage input: 220VAC±15% 60Hz)
F+ F- : direct ventilation output port
AL1 AL2: general alarm output port
A+ B- SGND: RS485 communication port
N: not connected pin
7. Control Board Diagram
7.1 Function and Application
ET731 intelligent air conditioner controller is a universal intelligent controller, controlling with highly integrated STC SCM. It can intelligently control thermostatic cabinet air conditioner working and hydrogen exhausting, including functions such as fault self diagnosis, power-on self start, or restart after unexpected failure caused by other reasons. The controller is compatible with all types of air conditioners in the market.
The controller, with the features of advanced performance, easy installation and setting, are widely used in telecom cabinet, small and medium sized telecom room, UPS room, outdoor base station room, etc.
7.2 Technical Parameter
- 2×16 Chinese/English shift LCD display, user friendly;
- Simultaneously display temperature and humidity inside the box and communication room temperature;
- Temperature measurement accuracy: 0.1 °C; humidity measurement accuracy:5%;
- Can store 180 days’ daily event record, 1 record every day;
- Daily highest temperature, lowest temperature, average temperatureDaily event record;
- Save the former day’s daily data at 0:00 every day; Can query 180 days’ daily record
- information;
- RS485 communication, YD/T 1363.1-2005 standard protocol, support remote detection and control;
- Control mode: pulse (Non dry contact air conditioner), conducting (dry contact air conditioner)
- Real-time control air conditioner on/off
- Power supply: AC185V~264V/60HZ;
- Power consumption:≤5W;
- Working environment: -30°C~70°C; <90%RH;
- Installation method: guide rail,hanging;
- Dimension(L*W*H):150mm×190mm×45mm
8. Mainboard Wiring Diagram
9. Packing and Shipping
Our Delivery Agent
The goods can be shipped by sea, by air, by courier, by land, by train, etc.
Besides the following delivery agent, we can also look for the delivery agent with the best price in china if you need us to do for you.
10. Our Contact Information
Mobile Phone: 0086-13752765943
Telephone: 0086-0755 66600941
Email: info@estel.com.cn
lxf.estel@hotmail.com
Skype: fiona.liang10
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.