High Efficiency Industrial Ups Battery Backup , 30KVA 24KW Large Ups Systems
IP42 Industrial UPS Power Supply Efficiency Up To 98%10 - 100KVA
High-reliability Industrial Grade Design:
The CNI310 system is composed of power special-purpose UPS, DBW regulator cabinet, PDU series feeder cabinet. CONSNANT Company apply herself to the development of China’s electricity demands for power plants, substations, power distribution products are designed with online double conversion, zero conversion function. Main applications include electric power long distance, RTU, power carrier wave, power monitoring and so on. When the utility power is normal, single phase 220V(or three phase 380V.) After isolation, rectification and filtering through the inverter to provide a stable power supply to the load; if the input AC power is abnormal or power failure, the backup power system by the DC screen provide power through non-return diode inverter. When the DC screen occurs voltage shortage or power break, the static switch transfer to bypass for power supply; when the electricity is restored, the inverter automatically switches to utility power and provide power supply under inverter mode. If the inverter overload or fault and transfer power supply under bypass mode, also give a warning signal at the same time.
Application:
Petroleum, chemical industry, gas and power station and so on.
Key features:
- Adopt full digital control technology
- Intelligent detection and monitoring function
- Digitally control the static switch with zero switch
- Full isolation between input and output
- Super low output zero earth voltage
- DC UPS isolated with utility power completely
- Cubical design with power standard (customization)
- Multifunctional protection for overvoltage, under voltage, over current, short circuit and over temperature and so on.
- Large-screen LCD monitor with Chinese and English operation interface
- Ultralong 256 event record, user-friendly analysis and management to the situation of the power supply (touch screen optional)
- Static bypass has a strong anti-overload capability
System:
- Operation temperature: 0ºC/ + 40ºC
- Relative humidity: <95% non condensing
- Color: Light gray (RAL 7035)
- Noise: 54dBA at 1m 60dBA at 1m 65dBA at 1m
- Protection degree: IP42
- Efficiency Smart Mode: Up to 98%
- Compliance Safety: EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive 2004/108/EC)
Unique option:
- SNMP card
- Dry contact card
- Signal transmitter
- Bypass isolation and voltage regulation
- Increase feeder circuit (standard for 8 loops)
- 12 pulse rectifier
- The appearance of special models(standard dimension:800×600×2260mm)
Technical parameter:
| CNI310 10-100KVA | ||||||||
| Model | 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA |
| Capacity | 8KW | 12KW | 16KW | 24KW | 32KW | 48KW | 64KW | 80KW |
| Input | ||||||||
| Rated voltage | 380/400/415 Vac three | |||||||
| Voltage range | ±20% | |||||||
| Frequency range | 50/60HZ±5% | |||||||
| Power factor | ≥0.8 | |||||||
| Current harmonic distortion | <5%with harmonic filter | |||||||
| Soft start | 0-100% in 10” | |||||||
| Bypass Input | ||||||||
| Rated voltage | 220/230/240Vac single-phase | |||||||
| Permitted voltage range | ±15%(selectable from ±10% to ±25% from front panel) | |||||||
| Rated frequency | 50/60Hz | |||||||
| Permitted frequency range | ±2%(selectable from ±1% to ±5% from front panel) | |||||||
| Standard features | BackFeed protection; split bypass line | |||||||
| Batteries | ||||||||
| Type | Maintenance-free lead-acid VRLA AGM / GEL;NICd | |||||||
| Maximum recharge current(A) | 0.2 X C10 | |||||||
| DC Voltage | 384VDC | |||||||
| AC ripple voltage | <1% | |||||||
| Inverter output | ||||||||
| Number of phase | 1 | |||||||
| Rated voltage(V) | 230Vac single phase | |||||||
| Regulation of the output voltage | 220~244Vac phase/neutral(from control panel) | |||||||
|
Crest factor (Ipeak/Irms) |
3:1 | |||||||
| Static stability | ±1% | |||||||
| Dynamic stability | ±5% | |||||||
| Frequncy | 50/60Hz configurable | |||||||
| Overload | 110% 125% 150% of the rated current for 5h/10'/1' | |||||||
| Frequency stability | ±0.05% on mains failure;±2%(selectable from ±1% to ±5%)with mains supply present | |||||||
| System | ||||||||
| Remote signaling | Volt free contacts | |||||||
| Remote controls | EPO and Bypass | |||||||
| Communication | RS232 + remote contacts | |||||||
| Weight(KG)N.M | 200 | 220 | 230 | 260 | 290 | 340 | 440 |
|
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.