High Output Load Three Phase UPS Systems Pure Sine Wave Low Input THDI
180KVA High Output Load Ability Modular UPS System With High Output PF
180KVA Modular Online High Output Load Ability Three Phase UPS System Pure Sine Wave High Efficiency
Brief Information:
CNM330 series is modular online UPS for sensitive equipment. The single cabinet power rating covers from 30KVA to 300KVA which delivers the best of combination of reliability, hot-swappable and flexibility. With the latest IGBT three-level technology and DSP control, CNM330 achieves a high input power factor, low THDi Modular design with N+X redundancy and online hot swapping ,easy to expand the capacity Full DSP control of high stability, reliability and safety Integrated IGBT module with improved performance and reduced size
Advantages:
- Hot-swappable
- High efficiency
- Front access
- Small footprint
- Wide input voltage range
- High power density
- Low input THDI and unity PF
- Pure sine wave output voltage
- High EMC performance
- Display language variety
- High overload capacity
- Battery recharge faster
- Low audible noise
- Self-Diagnosis
- Record data before failure
- Auto-calibration by Parametric set software
- Download history log in a easily readable
- Battery sharing
- Intelligent battery management
- Self aging
Wide Input voltage range
Application:
Application IDC(Internet Data Center)
Computing center
ISP (Internet Service Provider )
Telecom , Finance, bank and securities , Tax
Hospital system , industrial automation
Precision equipment, etc.
Specication:
| model | CNM330 |
| Input voltage | 380V/400V/415V (South American 208V option ,derating use) |
| Input Frequency | 50/60HZ |
| THDI | THDI<3% |
| Power Factor | Full load >0.99 half load>0.98 |
| Battery voltage | ±240VDC(default) 12V battery 30-40PCS can be choose |
| Bypass overload capacity |
Long term at 135% rated load, 150%<load<180% 10min , Load>1000% 100ms |
| Output voltage | 380/400V415VAC 3-phase 4-wire |
| Voltage Accuracy | ±0.5% (balanced load) ±1% (unbalanced load) |
| Power factor | 0.9 / 1 |
| Overload capacity | 110% 1H , 125% 10mins , 150% 1min , >150% 200ms |
| Communication ports | RS232 , RS458 , Dry contact , SNMP card , EPO , generator port |
| System efficiency | >96% at load above 50% , >95% at load above 25% |
(Optional South America 208V must be derating use)
Get in Touch