Smart Control Uninterruptible Power Supplies Industrial Automatic Demand
Static Switch Module UPS Uninterrupted Power Supply
SCR And AC Contactor In Parallel 300kVA - 1200kVA
High Availability Configuration Structure
- Static switch module: System standard configuration module. Adopts SCR and AC contactor in parallel. High reliability, strong overload ability: 1000% for 1 min. Transfer time is less than 1ms. Have strong self-detect, inter-lock and full-protection function.
- Power Module: Freedom choice of capacity configuration according demand, easy to expand; Online double-conversion design to ensure the output quality; Each module has independent digital intelligent control; Each module can work independently; Each module has a separate charging system; All modules can be hot-swappable, easy for online maintenance; Each UPS module provide 4.5KW charge capacity, equivalent to 10 to 12A
- Rich Management Interface: Advanced battery management, data recorder
- Advanced self-diagnosis:Inverter and rectifier circuit working condition monitoring, battery capacity and status detection, equipment working environment temperature testing, ease of maintenance and management of equipment, fan of fault detection(can replace the fan without power)
Application:
Application IDC(Internet Data Center)
Computing center
ISP (Internet Service Provider )
Telecom , Finance, bank and securities , Tax
Hospital system , industrial automation
Precision equipment, etc.
Features:
■ Superior energy saving
■ Easy-to-install
■ Easy-to-maintain
■ Easy-to-modify
■ Extra large LCD that can display 12 language (Chinese ,English ,Russian, French ,Spanish and so on)
■ Provide large LCD touch screen (optional)
■ Each UPS modules provide 4.5KW charge capacity. equivalent to 10 to 12A
■ Advanced DSP full digital control technologies realize higher system stability, online capacity expansion and maintenance
■ Advanced distributed active parallel technology realizes parallel operation of 4 UPS units and online capacity expansion without centralized bypass cabinet
■ Adaptive to severe power grid environment due to extra wide input voltage and frequency ranges
■ Intelligent battery management maintains battery automatically to prolong the battery life
■ The machine system for modular structure, consists of 1 to 10 module's biggest single module to 30kw
■ UPS power module supporting hot swappable, capacity upgrade extremely simple.
■ Super ability for overload and short circuit, ensure the system stability and safety under the limit state of system
Technical Specifications:
| Model | CNM330 20-300KVA | |
| Capacity | 20-300KVA | |
| Main Input | ||
| Input Voltage | 380V/400V/415V | |
| Input Frequency Range | 50/60Hz | |
| Power Factor | Full load>0.99 ,Half load >0.98 | |
| THDi | THDi<3% | |
| Input Power Soft-start Function | 5-30s settable | |
| Input Voltage Ranges | 228V-476V;-20%~25% at Full load ; linear derating at -25% ~- 40%; can take 70% load at -40% | |
| Frequency Range | 40-70HZ | |
| Battery | ||
| Battery Voltage | ±240VDC(Default),12V Battery 30~40pcs can be choose | |
| Charge Voltage Accuracy | ±1% | |
| Bypass | ||
| Bypass Input Voltage | 380/400/415VAC 3-phase 4-wire | |
| Voltage Range | Default value is -20%~+15%; -40%, -30%, -10% ~ +10%, +15% , other ranges can be set via software | |
| Overload Capacity | Long term at 135% rated load ,150%<load<180% more than 10 min, load>1000% 100ms | |
| Output | ||
| Inverter Output Voltage | 380/400/415VAC 3-phase 4-wire | |
| Voltage Accuracy | ±0.5% ( balanced load ) , ±1% ( unbalanced load ) | |
| THDV | THDV<1% (linear load) , THDV<3% (nonlinear load) | |
| Power Factor | 0.9 | |
| Three Phase Angle Accuracy | 120°± 0.5° | |
| Current Crest Ratio | 3:1 | |
| Overload Capacity | 110%1h,125%10mins,150%1mins,>150%200ms | |
| Transfer Time | 0ms,15ms (Eco Mode) | |
| System | ||
| Frequency | 50Hz/60Hz (Settable) | |
| Mains Synchronization Range | ±2Hz(Default value), adjustable with step of 0.5Hz within range of +/- 0.5Hz - 3Hz | |
| Protection Level | IP20 | |
| Communication Ports | RS232,RS485,dry contact, SNMP card, EPO, generator port | |
| System efficiency | >96% at load above 50%, >95% at load above 25% | |
| Operation Temperature | 0-40ºC | |
| Storage Temperature | -25ºC~70ºC ( without battery) | |
| Humidity | 0-95% (no-condensing) | |
| Noise(dB) | 55-62dB,Adjusted with load | |
| Weight | module:PM20 | 20KVA power module : 30KG |
| module:PM30 | 30KVA power module : 35KG | |
| module:PM40 | 40KVA power module : 40KG | |
| Dimension (W x D x H)mm | 3 module cabinet | 600X900X1135 |
| 5 module cabinet(5 battery cabinet option) | 600X1100X2070/ | |
| 6 module cabinet | 600X900X1535 | |
| 10 module cabinet | 900X900X2080 | |
| power module | 440X650X132(3U)(10KVA/20KVA/30KVA) | |
(Optional South America 208V must be derating use)