Rack Mounted Multi Function Inverter CNR110 3500-24 4.5KW 24VDC
Rack-Mounted Inverter Control Machine CNR110 5500-48 5.5KW 48VDC
INTRODUCTION
This is a multi-function inverter/charger, combining functions of inverter, solar charger and battery charger to offer uninterruptible power support with portable size.
Features
Configurable battery charging current based on load requirements.
Configurable Mains/Solar Charger priority via LCD setting.
Configurable mains input voltage range for home appliances and personal computers via load requirements.
Remote monitor function via SNMP Card(optional).
SPECIFICATIOS
| Model | 3.5KW | 5.5KW |
| Input Voltage Waveform | Sinusoidal (utility or generator) | |
| Nominal Input Voltage | 230Vac | |
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) | |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | |
| High Loss Voltage | 280Vac±7V | |
| High Loss Return Voltage | 270Vac±7V | |
| Max AC Input Voltage | 300Vac | |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
| Low Loss Frequency | 40±1Hz | |
| Low Loss Return Frequency | 42±1Hz | |
| High Loss Frequency | 65±1Hz | |
| High Loss Return Frequency | 63±1Hz | |
| Output Short Circuit Protection | Circuit Breaker | |
| Efficiency (Mains Mode) | > 95% | |
| ( Rated load, battery full charged ) | ||
| Transfer Time | 10ms typical(UPS); 20ms(Appliances) | |
| Output power derating: When AC input voltage drops to 170V, the output power will be derated. |
![]() |
|
1. LCD display
2. Function Keys
3. Status indicator
4. Charging indicator
5. Fault indicator
6. Power ON/OFF switch
7. Breaker
8. Mains input
9. Mains output
10. RS-232 communication port
11. PV input
12. Battery Positive Industrial Connector
13. Battery Negative Industrial Connector
14. SNMP smart card slot
SAFETY INSTRUCTIONS
1. Before using this unit, read all instructions and cautionary marking on the unit, the batteries and all appropriate sections of this manual.
2. To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
3.Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric or fire.
Get in Touch