1500/5A Protection Split Core AC Current Sensor Dry Type Insulated Resin Poured

Price Negotiable
Price: Negotiable
MOQ: 1 Pieces
Delivery Time: 3 - 7 Days
Brand: GFUVE
Product Description

 

 

1500/5A Resin Measuring and Protection Split Core Dry Type CT

 

 

This Model is is suitable forcurrent measurement and microcomputer protection of electrical equipment in 10KV and 35KV AC power system.

 

The transformer can be directly installed at the inlet andoutlet cables.The slice is imported silicon material. Thesemicircular ring core and secondary windings arevacuum poured by insulated resin.

 

Parameters

 

Technical parameters  
Standards IEC60044-1; IEC 61869-2; NTC 2205; ANSI C57.13; GB1208-2006
Rated primary current 100-1500A
Rated load ≤10VA
Rated frequency 50Hz or 60Hz
Rated secondary current 5A or 1A
Rated short-time thermal current 40kA, 1S
Rated continuous thermal current 120%I1n
Secondary winding power-frequency voltage 3kV, 1min
Instrument security factor FS≤10
Mechanical parameters  
Dimensions (W×D×H) (mm) φ80xφ110x50
Weight (kg) 2.1
Operating conditions  
Operating temperature -35°C to +55°C
Daily average temp <+40°C
Storage temperature -40°C to +70°C
Altitude <3500 meters
Condition No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.

 

 

Datasheet

 

 

Type LZCK720-10 LZCK720-10
Purpose Measuring current transformer Protection current transformer
Ratio Accuracy class and rated load(VA) Accuracy class and rated load(VA)
I1/I2 0.5 1 10P10 10P5
100/1 2 2.5   1
200/1 2.5 3.75   2.5
300/1 3.75 5 2.5 3.75
400/1 5 7.5 3.75 5
500/1 7.5 10 5 7.5
600/1 10 15 7.5 10
100/5 2 2.5   1
200/5 2.5 3.75   2.5
300/5 3.75 5 2.5 3.75
400/5 5 7.5 3.75 5
500/5 7.5 10 5 7.5
600/5 10 15 7.5 10
800/5 10 15 7.5 10
1000/5 10 15 7.5 10
1200/5 10 15 7.5 10
1500/5 10 15 7.5 10

 

 

 

Outline Drawing

 

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
Location Oriental HuaRui A, No. 150 Guanzhuang Road, Chaoyang District, Beijing, 100024, China
Contact Person Andy

Request A Quote

Please check your email address.
Your message must be at least 20 characters.