TEST-630 smart automatic 3 phase portable protection relay test set equipment with harmonics output

 

 

Universal testing system TEST-630 (6×35A, 6×300V) can test all types of protective relays, including modern IEC61850 based
relays. Other test works, such as transducer, energy meter, indication meter, etc., can also be done easily. It's the ideal test
device for all power utilities, power plants, relay manufactures, panel manufactures, research institutes, Universalities, testing
companies, etc.
TEST-630 is designed with fuse on the mains supply and electronic protection for overload on the current (open circuit) or voltage outputs(short circuit), with immediate isolation of the output and alarm indication. Also diagnostic message for the setting of wrong data, mistakes on the input etc. There's also electronic protection in case of counter-feed of voltage output, if any incorrectness happen, the alarm light shall flash. And Overheat LED indicator shall flash for Protection against over-temperature, on all outputs.
 
Differential
is suitable for use the 6 output current channels' relay tester, which is applied on transformer, generator and bus bar etc. differential protection equipment test. Because of adopting the 6 currents output, it realizes the two sides three phases test between relay tester and relay equipment.
Inverse time overcurrent
This module realizes the directional over-current test and non-directional over-current test. This module also include: testing positive sequence, negative sequence and zero sequence instantaneous time over-current,
over-heat protection inverse time over-current or the customized “Current/Time” operation characteristic.

TEST ITEM

  • U/I test
  • DC test
  • Impedance characteristics
  • Power direction test
  • I-T test
  • Differential relay
  • Harmonic test
  • Differential protection
  • Distance protection
  • Zero sequence protection
  • Setting group test
  • State sequence
  • Synchronization test
  • Special test
  • Oscillation test
  • Metering instrument
  • Hardware checkout
  • Low Voltage protection
  • Fault Recurrence

 

 

PARAMETERS

Electrical parameters
Power voltage AC220V±10% or AC110V±10%, 50/60Hz±10%
Time measurement 0.1ms-999999.999s
AC current output 
Phase current output (effective value) 3 x 0-30A
Maximum power output 260VA/phase
Maximum parallel current output (effective value) 0-90A
Long-term allowable working value of phase current
(effective value)
>10A
Allowable working time of maximum current >11s
Accuracy class <±0.2%
AC voltage output 
Phase voltage output (effective value) 5 x 0-130V
Line voltage output (effective value) 0-260V
Maximum power output 70VA/phase
Accuracy class <±0.2%
DC current output 
Output range -10 to 10A or 3 x 0 to ±10A
Maximum power output 200VA
Accuracy class <±0.2%
DC voltage output 
Output range 0-300V or 5 x 0 to ±130V
Maximum output power 130VA
Accuracy class <±0.2%
Binary input 
Idle contact 1-20mA, 24V (DC)
Electric potential contact 250V/0.5A (DC)
Binary output 
Idle contact 250V/0.5A (DC)
Rated output 
Frequency error <±0.01Hz
Phase error <±0.2°
Waveform distortion <±0.3% (fundamental wave)
Time error <40µs
Output frequency 0-1050Hz
Superposed harmonic wave 0-21times

PHOTO

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
Location Oriental HuaRui A, No. 150 Guanzhuang Road, Chaoyang District, Beijing, 100024, China
Contact Person Andy

Request A Quote

Please check your email address.
Your message must be at least 20 characters.