OPzS 2V1200Ah Flooded Gel Electrolyte Battery with 20+ Year Life and 85Kg Weight

Price Negotiable
Price: Negotiable
MOQ: Negotiable
Delivery Time: 30 Days
Product Description
OPzS Series 2V1200Ah Flooded Gel Electrolyte Battery
Product Overview

The OPzS series is a traditional tubular plate flooded battery designed for maximum efficiency and reliability across diverse applications. With a design life exceeding 20 years according to IEC60896-11 standards, this battery delivers exceptional performance in demanding environments.

Key Features
  • 20+ years design life at floating condition
  • Wide operating temperature range from -40°C to 65°C
  • Tubular positive plate with prolonged cycle life
  • Nano Silica gel electrolyte technology
  • Lead Calcium die cast grid with enhanced corrosion resistance
  • Excellent deep discharge recovery capability
  • Low self-discharge rate (approx. 4% per month)
  • Long shelf life (1 year at 20°C)
Technical Specifications
Parameter Specification
Nominal Voltage 2V
Nominal Capacity 1200 Ah @ C10 (to 1.80Vpc)
Dimensions L275mm × W210mm × H700mm
Weight Without electrolyte: 62Kg
With electrolyte: 85Kg
Terminal Type Female Copper Insert M8 (torque: 10-12N.m)
Internal Resistance Approx. 0.70mOhm (fully charged @ 25°C)
Max Charge Current 240A
Max Discharge Current (5S) 2500A
Short Circuit Current 5000A
Float Charge Voltage 2.21-2.25V @25°C (-3mV/°C/cell)
Equalize Charge Voltage 2.35-2.4V @25°C
Construction Details
  • Positive Plate: Tubular plate with die cast alloy grid
  • Negative Plate: Balanced Pb-Ca grid for improved recombination efficiency
  • Separator: Leaf shape rubber separator
  • Electrolyte: Dilute high purity sulphuric acid of 1.240 specific gravity
  • Battery Container: SAN material
  • Battery Cover: ABS material
  • Pillar Seal: Double layers epoxy resin seal
  • Relief Valve: Complete with integrated flame arrestor
Performance Characteristics
Constant Current Discharge Characteristics Chart
Constant Power Discharge Characteristics Chart
Battery Charge Characteristic Curve
Battery Discharge Characteristic Curve
Cycle Life vs Depth of Discharge Graph
Capacity vs Temperature Performance Chart
Cycle Discharge Voltage Curve Diagram
Applications
  • Standby Power Systems requiring highest reliability and security
  • Solar and Wind Energy Storage Systems
  • Telecommunication Infrastructure

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Wuhan Future Intepower Co., Ltd.
Location Room 316, Unit 3 Zhihui Building, 0601 Area of Jianhan, Economic Development Zone, Jianhan District, Wuhan, Hubei, China , Jianghan District, Wuhan, China
Contact Person Wendy (Jiang Wei)

Request A Quote

Please check your email address.
Your message must be at least 20 characters.